background image

5. Measure liquid refrigerant pressure at the service valve by

attaching an accurate pressure gauge to the service port
and record the pressure.

NOTE: When only the lead compressor is running, the

suction pressure will be higher than a standard
single speed system, or  a dual compressor sys-
tem with both compressors  running. This is a
normal operation for a dual compressor system
operating with a large indoor coil at part load
capacities.

6. Refer to the Table 3 to find the recommended subcooling

temperature.

7. Refer to Table 4 to determine the proper liquid line tempera-

ture at the point where the "Required Subcooling Tempera-
ture" and "Measured Liquid Pressure"(from step 5)
intersect. Record the required liquid line temperature. 

8. Measure the liquid line temperature by attaching an accu-

rate electronic thermometer or a thermistor at the liquid line
near the condensing unit.

9. If the liquid line temperature is higher than the value deter-

mined in step 7, add refrigerant charge carefully until the
recommended subcooling temperature is obtained at the
corresponding liquid line pressure.

CAUTION: D O N O T  OV ER C H AR GE   TH E  S Y ST EM ,

THIS COULD  LEAD TO  DAMAGE TO THE
COMPRESSORS.

It is suggested to maintain the recommended subcooling
levels indicated in Table 4, within  

±

°

F.  Too low a subcool-

ing or too high a subcooling will result in poor performance
of the air conditioning unit. 

NOTE: If liquid line temperature is lower, remove and
recover the refrigerant charge until the recommended sub-
cooling temperature is obtained.

EXAMPLE:

Given an H1DS036 with only the lead compressor operating
on first stage.

1. Liquid pressure at the service valve = 179 lbs.
2. Recommended subcooling temperature from Table 3.
    = 10 

°

F

3. Required liquid line temperature  from Table 4 = 84 

°

F

If the measured liquid line temperature at the liquid line near
the condensing unit  = 89 

°

F, then the actual level of subcooling

based on Table 4 = 5

°

F

Therefore,  add charge to reach required liquid line tempera-
ture given in Step 3, thereby,  reaching the recommended
subcooling level in Step 2 above.

If the measured liquid line temperature at the liquid line near
the condensing unit = 79 

°

F, then the actual  level of subcooling

based on Table 4 = 15 

°

F.

Therefore, remove and recover charge to reach required liquid
line temperature given in Step 3, thereby,  reaching the recom-
mended subcooling level in Step 2.

Once the charge is established when the lead compressor is
running, it is not necessary to establish the charge once again
when both compressors are running. However it is recom-
mended to energize the second compressor to verify system
performance.

APPROVED SYSTEM COMBINATIONS

(Outdoor Unit / Variable Speed Air Handler & Coil)

CONDENSING UNIT

FACTORY CHARGE

LBS. -  OZ.

INDOOR COIL

 ADJUSTMENT

CHARGE, OZ.

H1DS036

N1VSD14

G3HC / G1FC036

9 - 9

+0

G3HC / G1FC042

+0

N2VSD20

G3HC / G1FC048

+0

G3HC / G1FC060

+14

H1DS048

N2VSD20

G3HC / G1FC048

9 - 9

+0

G3HC / G1FC060

+14

H1DS060

N2VSD20

G3HC / G1FC060

14 - 6

+0

TABLE 5 - CHARGE ADD STANDARD COILS

UNIT 

SIZE

LIQUID LINE OD

VAPOR

LINE OD

R22 CHARGE

OZ / FT

036, 048, 060

3/8

7/8

0.70

TABLE 6 - REFRIGERANT LINE CHARGES

550.37-N1Y

10

Central Environmental Systems

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: