background image

SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

This unit is equipped with crankcase heaters for both the lead
and follower compressors. The operation of the crankcase
heater is monitored by means of the control board.

CAUTION:  An attempt to start the compressor without at least

8 hours of crankcase heat will damage the com-
pressor.

A warning label with an adhesive back is supplied in the unit
installation instruction packet. This label should be attached to
the field supplied disconnect switch where it will be easily seen.
See below.

In order to energize the crankcase heater:

- Set indoor two stage cooling thermostat to "OFF" position.

- Close the line power disconnect to the unit.

CHECKING  SYSTEM CHARGE

The factory charge in the outdoor unit is listed in the Table 5 as
well as unit nameplate and includes enough charge for the unit
and the corresponding indoor evaporator coil. This unit in-
cludes sufficient charge for 15 feet of line sets. Table 6 lists the
refrigerant line charges for additional lengths.

CAUTION:

REFRIGERANT CHARGING SHOULD ONLY BE
CARRIED OUT BY A QUALIFIED AIR CONDI-
TIONING CONTRACTOR.

In order to check whether the unit has the required charge in
the system, follow the procedure described below.

WARNING:DO NOT VENT REFRIGERANT TO THE ATMOS-

PHERE. IT IS NECESSARY TO RECOVER THE
REFRIGERANT DURING ANY REPAIR OR IN-
STALLATION OF THE SYSTEM.

1. Set room thermostat at desired temperature. The thermo-

stat may be energized at first (Y1) stage or second (Y2)
stage. If only the first stage (Y1) is energized, only the lead
compressor will be in operation. Both the compressors will
be in operation if the second stage of thermostat (Y2) is
energized.

Set room thermostat at "COOL" position and fan switch at
"AUTO" or "FAN" position. There is a five minute delay
when the "system control board" is powered for the first
time. Refer to "System Functions" for more information
about time delays.

2. Operate the unit for a minimum of 15-20 minutes before

checking the charge.

3. Verify the desired indoor air handler air flow (CFM). 

4. The system charge should be varified with only the lead

compressor running, however it can be also checked with
both the compressors running at the same time at the rated
indoor air handler air flow.  However, it is required to estab-
lish the subcooling level at any one condition i.e. either with
the lead compressor running or when both (the lead and
follower) compressors are running.Recommended sub-
cooling temperature is listed in Table 3.

MODEL

RECOMMENDED SUBCOOLING 

°

F

LEAD

COMPRESSOR

ONLY

LEAD + FOLLOWER*

(BOTH)

COMPR. RUNNING

H1DS036

10

18

H1DS048

10

18

H1DS060

10

18

*Lead compressor is designated / labeled as  the # 1 com-
pressor. Follower compressor is the # 2 compressor.

TABLE 3 - RECOMMENDED SUBCOOLING

LIQUID

PRESSURE

(PSIG) @
SERVICE

PORT

Required Subcooling Temp. 

°

 F

LIQUID

PRESSURE

(PSIG) @
SERVICE

PORT

Required Subcooling Temp. 

°

 F

5

10

12

15

20

5

10

12

15

20

Liquid Line Temperature 

°

 F

Liquid Line Temperature 

°

 F

139

73

68

66

63

58

264

116

111

109

106

101

146

76

71

69

66

61

271

117

112

110

107

102

153

79

73

71

68

63

276

120

115

113

110

105

161

82

77

75

72

67

285

122

117

115

112

107

166

85

90

88

85

80

301

126

121

119

116

111

179

89

84

82

79

74

309

127

122

120

117

112

187

92

87

85

82

77

317

130

125

123

120

115

196

95

90

88

85

80

325

132

127

125

122

117

202

97

92

90

87

82

333

134

129

127

124

119

208

99

94

92

89

84

342

136

131

129

126

121

220

103

98

96

93

88

350

138

133

131

128

123

229

106

101

99

96

91

359

140

135

133

130

125

236

108

103

101

98

93

368

142

137

135

132

127

246

111

106

104

101

96

377

144

139

137

134

129

256

114

109

107

104

99

386

146

141

139

136

131

TABLE 4 - SUB-COOLING CHART

IMPORTANT

IF POWER HAS BEEN OFF FOR 8 HOURS OR LONGER,
DISCONNECT SWITCH MUST BE TURNED ON 8 HOURS
BEFORE THERMOSTAT IS SET TO “HEAT”,"COOL" OR
“AUTO”
                                    035-03095. 

550.37-N1Y

Central Environmental Systems

9

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: