background image

RECORDING TOTAL SYSTEM CHARGE

The factory charge in the outdoor unit is listed in Table 5 and
includes enough charge for the unit, matched evaporator and
15 feet of lines. Installations over 15 feet long and some indoor
coil matches may require some additional charge.  Table 6  lists
the refrigerant line charges.

The “TOTAL SYSTEM CHARGE” must be permanently
stamped on the unit data plate.

Total system charge is determined as follows:

1. Determine the condensing unit charge from Table 5.

2. Determine  indoor coil adjustment charge from Table 5.

3. Calculate the additional charge for line lengths greater than

15 feet using Table 6 factors.

4. Total system charge = Item 1 + Item 2 + Item 3.

5. Permanently stamp the unit data plate with the total amount

of refrigerant in the system.

SYSTEMS FUNCTIONS

The dual compressor Stellar ULTRA  air conditioner has unique
system functions as described below.

COOLING OPERATION

The condensing unit utilizes a two stage cooling indoor thermo-
stat. Depending on the cooling load requirements, the com-
pressors are energized in sequence by means of the two stage
thermostat.

With a call for first stage cooling (Y1), the outdoor fan and the
lead compressor are energized. Simultaneously, the variable
speed indoor blower motor is also energized and the blower
delivers the corresponding airflow adequate for the first stage
cooling load.

With a call for second stage cooling (Y2), the follower compres-
sor is also energized. Simultaneously, the variable speed
blower now delivers the rated CFM  in order to satisfy the
cooling demand. The follower compressor is energized only
when cooling demand is not met by the lead compressor
running alone. Once the second stage building load is satisfied,
the unit will operate with only the lead compressor, until  first
stage  indoor cooling thermostat is satisfied, or if there is a call
for second stage cooling operation.

SYSTEM CONTROL BOARD OPERATIONS

The Stellar ULTRA air conditioner utilizes a control board to
control as well as monitor the operation of the two stage cooling
system. The following is an overview of the functions of the
control board.

Control Board LED Functions

The control board used to control and monitor the operation of
the two stage cooling system has a LED mounted on the board,
which provides signals (Fault Codes) for several system op-

erations. See Table 7, which provides a list of LED functions
and definitions.

Power Supply

The five minute control board time delay is energized by means
of 24V power supply from the transformer installed in the indoor
variable speed air handler.  As soon as the control board
receives power, it warms up for five minutes before it starts
operating. The control board also has a 3A fuse which protects
the control board from short circuiting.

Five Minute Time Delay (Control Board)

Every time the control board is powered after a power interrup-
tion,  it will delay the operation for five minutes . The LED light
on the control board will blink "ON" for 1 second and  "OFF" for
4 seconds, indicating a warm up period for the control board.
This will prevent the unit from short cycling. 

Five Second Time Delay

A five second time delay is energized every time the board
receives a control signal Y1 or Y2 from the thermostat. This
prevents cycling of the unit and unnecessary operation of the
unit as a result of thermostat jiggling.

One Minute Inter Stage Time Delay

Anytime the unit receives a call for second stage cooling
operation (Y2) from the thermostat,  when the lead compressor
is operating, there is a one minute time delay before the
follower compressor will start. The outdoor fan motor and the
lead compressor continue to run during this inter-stage time
delay.

Five Minute Time Delay (Compressor 1 and 2)

A  five minute time delay prevents the system from short cycling
after a thermostat off cycle or power interruption.

There is a five minute time delay for both, the lead and the
follower compressor after a thermostat off cycle. These delays
are incorporated to prevent the short cycling of the unit. How-
ever, during the five minute delay on the follower compressor,
the lead compressor and the outdoor fan will continue to run,
together with the indoor variable speed air handler, if the call
for cooling still exists.

For servicing or during installation of the condensing unit, the time
delay may be overridden by momentarily jumpering the test
terminal and "R" terminal on the board if necessary.  However,
the jumper must be removed during normal operation.

Pressure Switches

High and low pressure switches are installed and wired in
series. They provide addtional protection for the system if any
abnormal operating conditions occur.  If the control board
senses a tripping of the high or low pressure switch, the control
will provide a five minute delay before the system starts oper-
ating again. The LED will blink rapidly indicating that there is a

550.37-N1Y

Central Environmental Systems

11

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: