background image

CAUTION:  If visual verification of the valve stem reaching the

retaining ring is impossible, stop backing out the
valve stem when the slightest increase in resis-
tance is felt. Because of the small size and there-
fore the reduced resistance, back out the liquid
valve 5 turns maximum to prevent going past the
retaining ring.

WARNING:  If the valve stem is backed out past the retaining

ring, the O’ring can be damaged causing leakage
or system pressure could force the valve stem out
of the valve body possibly causing personal injury.
In the event the retaining ring is missing, do not
attempt to open the valve.

Replace plunger cap finger tight, then tighten an additional 1/12
turn (1/2 hex flat). Cap must be replaced to prevent leaks.

LINE CONNECTION

Connect the refrigerant lines using the following procedure:

1. Remove the cap and Schrader core from both the liquid and

vapor angle valve service ports at the outdoor unit. Connect
low pressure nitrogen to the liquid line service port.

2. Braze the liquid line to the liquid valve at the outdoor unit.

Be sure to wrap the valve body with a wet rag. Allow the
nitrogen to continue flowing.

3. Carefully remove the rubber plugs from the evaporator

liquid and vapor connections. 

CAUTION: The evaporator is pressurized.

4. Braze the liquid line to the evaporator liquid connection. The

nitrogen should now be flowing through the evaporator coil.

5. Slide the grommet away from the vapor connection at the

coil. Braze the vapor line to the evaporator vapor connec-
tion. After the connection has cooled, slide the grommet
back into original position.

6. Protect the vapor valve with a wet rag and braze the vapor

line connection. The nitrogen flow should be exiting the
system from the vapor service port connection. After this
connection has cooled, remove the nitrogen source from
the liquid fitting service port.

7. Evacuate the vapor line, evaporator and the liquid line, to

1000 microns or less.

8. Leak test all refrigerant piping connections including the serv-

ice port flare caps to be sure they are leak tight. DO NOT
OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).

NOTE: Do not use the system refrigerant in the outdoor unit

to purge or leak test.

9. Do not remove the flare caps from the service ports except

when necessary for servicing the system.

CAUTION: Do not connect manifold gauges unless trouble is

suspected. Approximately 3/4 ounce of refrigerant
will be lost each time a standard manifold gauge is
connected.

10. Release the refrigerant charge into the system. Open both

the liquid and vapor valves by removing the plunger cap
and with an allen wrench back out counter-clockwise until
valve stem just touches retaining ring. See Figure 7. Re-
lease the refrigerant charge into the system.  See "Precau-
tions During Brazing Angle Valves" on page 4 and 5.

11. If the refrigerant tubing, indoor evaporator coil or outdoor

condensing unit has developed a leak during shipment,  or
was, for any other reason, opened to the atmosphere for
more than four (4) minutes, it is necessary to evacuate the
system down to at least 1000 microns to eliminate contami-
nation and moisture in the system.

If a leak is suspected, leak test  to locate the leak. To verify
the  leak, close the valve to the vacuum pump suction to
isolate the pump and hold the system under vacuum. If the
micron gauge indicates a steady and continuous rise after
a few minutes, it’s an indication of a leak. If the guage shows
a rise, then levels off after a few minutes and remains fairly
constant, its an indication that the system is leak free, but
still contains moisture and may require further evacuation
if the reading is above 1000 microns.

WARNING: Never attempt to repair any brazed connections

while the system is under pressure. Personal injury
could result.

See "System Start Up" section for checking and recording
system charge.

FIGURE 6 - HEAT PROTECTION

ANGLE
VALVE

PLUNGER
CAP

FIGURE 7 - REMOVING PLUNGER CAP

550.37-N1Y

Central Environmental Systems

5

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: