background image

LOCATION

Before starting the installation, select and check the suitability
of the location for both the indoor and outdoor unit. Observe all
limitations and clearance requirements.

The outdoor unit must have sufficient clearance for air entrance
to the condenser coil, for air discharge and for service access.
See Figure 1.

If the unit is to be installed on a hot sun exposed roof or a
black-topped ground area, the unit should be raised sufficiently
above the roof or ground to avoid taking the accumulated layer
of hot air into the outdoor unit.

Provide an adequate structural support.

GROUND INSTALLATION

The unit may be installed at ground level on a solid base that
will not shift or settle, causing strain on the refrigerant lines and
possible leaks. Maintain the clearances shown in Figure 1 and
install the unit in a level position. Isolate the base from the
structure to avoid noise or vibration transmission.

Isolate the unit from rain gutters to avoid any possible wash out
of the foundation.

Normal operating sound levels may be objectionable if the unit
is placed directly under windows of certain rooms (bedrooms,
study, etc.).

ROOF INSTALLATION

When installing units on a roof, the structure must be capable
of supporting the total weight of the unit, including a pad, lintels,
rails, etc., which should be used to minimize the transmission
of sound or vibration into the conditioned space.

UNIT PLACEMENT

1. Provide a base in the pre-determined location.

2. Remove the shipping carton and inspect for possible damage.

3. Compressor tie-down bolts should remain tightened.

4. Position the unit on the base provided.

5. Sit unit on the (4) rubber elevating grommets provided with

the unit. These should be positioned as shown in Figure 2
to reduce noise and allow for proper drainage.

6. Make a hole(s) in the structure wall large enough to acco-

modate the insulated vapor line, the liquid line and the wiring.

TXV INSTALLATION

This condensing unit requires the installation of a thermal
expansion valve.   The TXV controls the superheat of the
refrigerant at the outlet of the evaporator coil, ensuring the
proper refrigerant temperature at the suction of compressor.
Following are the basic steps for installing the TXV. For detail
instructions, refer to the Installation Instructions accompanying
the TXV kit.

Install TXV kit as follows:

1. Position the interconnecting refrigerant lines for proper

installation to the outdoor condensing unit and the indoor
evaporator coil, but do not make any connections at this
time.

WARNING: The evaporator coil is under 15 psig pressure.

2. Crack open the liquid line fitting of the indoor coil to relieve

pressure. This fitting is left handed thread. Turn clockwise
to open.

3. Remove the fitting.

4. Using a small diameter wire, remove the orifice from the

other half of the liquid line fitting. 

NOTE: Orifice is not used when the TXV assembly is installed.

5. Reinstall the liquid line fitting hand tight and turn an addi-

tional 1/8 turn to seal well.

6. Insert and braze the TXV outlet connection to the liquid line

flare fitting mounted on the evaporator coil.

7. Connect external equalizer tube to the vapor line.

8. Position sensing bulb on horizontal portion of vapor line.

Secure using the clamps furnished in the kit. See Figure 3.
for positioning of the bulb. Insulate bulb after installation.

RUBBER
ELEVATING
GROMMETS
(4)

UNIT
BASE
PAN

Note: Do Not  block 
drainage holes with
grommets.

FIGURE 2 - POSITIONING GROMMETS

FIGURE 3 - CORRECT BULB LOCATIONS

7/8"  VAPOR LINE

ROTATE BULB TO KEEP
TAIL AT BOTTOM

SENSING
BULB

10 O'CLOCK

2  O'CLOCK

OR

END VIEW

550.37-N1Y

Central Environmental Systems

3

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: