background image

system error. The LED will blink "ON" for 1 second and "OFF"
for 1 second during the opening of either high or low pressure
switches. If four trips occur within 30 minutes, the control board
logic will lock out the outdoor unit, preventing operation. The
unit can be operated again by resetting the indoor two stage
cooling thermostat once the lockout condition is resolved.

Crankcase Heater Operation

The control board will energize the crankcase heater during the
condensing unit "OFF" cycle.

Condensing Unit Fan Operation

The control board will energize the condensing unit fan anytime
the compressor is operating. The outdoor fan will remain ener-
gized during the "One Minute Inter-Stage Time Delay". How-
ever, the fan will not remain energized, if either, the High or Low
pressure switches trip.

INSTRUCTING THE OWNER

Assist owner with processing warranty cards. Review Owners
Guide and provide a copy for the owner guidance on proper
operation and maintenance. Instruct the owner or the operator
how to start, stop and adjust temperature setting.

When applicable, instruct the owner that the compressor is
equipped with a crankcase heater to prevent the migration of
refrigerant to the compressor during the “OFF” cycle. The
heater is energized only when the unit is not running. If the main
switch is disconnected for long periods of shut down, do not
attempt to start the unit 8 hours after the switch has been
connected. This will allow sufficient time for all liquid refrigerant
to be driven out of the compressor.

The installer should also instruct the owner on proper  opera-
tion and maintenance of all other system components.

INDICATIONS OF PROPER OPERATION

Cooling operation is the same as any conventional air condi-
tioning unit.

The following checks may be made to determine if the system
is operating properly:

1. The outdoor fan should be running, with warm air being

discharged from the top of the unit.

2. The indoor blower (furnace or air handler) will be operating,

discharging cool air from the ducts.

3. The vapor line at the outdoor unit will feel cool to the touch.

4. The liquid line at the outdoor unit will feel warm to the touch.

If unit is not operating properly, check the following items before
calling a serviceman:

1. Indoor section for dirty filter.

2. Outdoor section for leaf or debris blockage.

Eliminate problem, turn off the thermostat for 10 seconds and
attempt start. Wait 5 minutes. If system does not start, call
service technician.

MAINTENANCE

1. Dirt should not be allowed to accumulate on the outdoor

coils or other parts in the air circuit. Clean as often as
necessary to keep the unit clean. Use a brush, vacuum
cleaner attachment, or other suitable means.

2. The outdoor fan motor is permanently lubricated and does

not require periodic oiling.

3. If the coil needs to be cleaned, it should be washed with

Calgon CalClean (mix one part CalClean to seven parts
water). Allow solution to remain on coil for 30 minutes
before rinsing with clean water. Solution should not be
permitted to come in contact with painted surfaces.

4. Refer to the furnace or air handler instructions for filter and

blower motor maintenance.

5. The evaporator coil drain pan should be inspected and

cleaned regularly to prevent odors and assure proper drain-
age.

WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER’S APPROVAL.

P.O. Box 1592, York, Pennsylvania USA 17405-1592
Subject to change without notice.   Printed in U.S.A
Copyright

 

 by York International Corporation 1994.  All Rights Reserved.

550.37-N1Y

LED DISPLAY

DEFINITION

LED LIGHT "ON" (No Flashing)

Normal Operation

FLASH (1 Second) PAUSE (4 Seconds)

Control Board Warm-up Operation

FLASH (1 Second) PAUSE (1 Second)

High or Low Pressure Switch Trip

RAPID FLASHES

High or Low Pressure Switch Lockout

LED LIGHT "OFF"

No Power Supply or Board Failure

TABLE 7 - LED FUNCTIONS

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: