THERMOSTAT
NEC CLASS 1
WIRING
WEATHERPROOF
DISCONNECT
SWITCH
NOTE: ALL OUTDOOR WIRING MUST
BE WEATHERPROOF
TO POWER
SUPPLY
12" REAR AND
SIDES
CLEARANCE
REQUIRED
TO
BLOWER
MOTOR
RELAY
TO
COIL
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
24" SERVICE
ACCESS CLEARANCE
REQUIRED
48" OVERHEAD
CLEARANCE
REQUIRED
NEC CLASS 2
WIRING
Sit unit on
rubber
elevator
grommets
to reduce
noise and
allow for
proper
drainage.
FIGURE 1- TYPICAL INSTALLATION
MODEL H1DS...
036
048
060
UNIT SUPPLY VOLTAGE
208/230-1-60
NORMAL VOLTAGE RANGE
1
187 to 252
MIN. CIRCUIT AMPACITY
20
25.9
30.5
MAX. OVERCURRENT DEVICE AMPS
2
25
35
40
COMPRESSOR # 1 AMPS
(Lead Compressor)
RATED LOAD
8.3
8.3
10.9
LOCKED ROTOR
48
48
64
COMPRESSOR # 2 AMPS
(Follower Compressor)
RATED LOAD
9.0
13.5
15.1
LOCKED ROTOR
48
68
81.0
CRANKCASE HEATER
YES
YES
YES
FAN MOTOR AMPS
RATED LOAD
0.7
0.7
0.7
LOCKED ROTOR
0.8
0.8
0.8
MIN. FIELD WIRE SIZE AWG
60
°
C COPPER CONDUCTORS
10
10
8
MAX. WIRE LENGTH FEET
BASED ON 3% VOLTAGE DROP
208V
125
100
100
230V
140
115
110
FAN DIAMETER INCHES
24
24
24
FAN MOTOR
RATED HP
1/10
1/10
1/10
NOMINAL RPM
825
825
825
NOMINAL CFM
2800
2800
2700
COIL
FACE AREA SQ. FT.
23.5
23.5
23.5
ROWS DEEP
1
1
2
FIN / INCH
20
20
16
LIQUID LINE OD
3/8
3/8
3/8
VAPOR LINE OD
7/8
7/8
7/8
OPERATING WEIGHT LBS.
277
282
340
1
Utilization range “A” in accordance with ARI standard 110.
2
Dual element fuses or HACR circuit breaker.
TABLE 1 - PHYSICAL AND ELECTRICAL DATA
550.37-N1Y