background image

LIMITATIONS

These units must be installed in accordance with all national

and local safety codes. If no local codes apply, installation must

conform with the appropriate national codes. See Table 1 for

unit application data. Units are designed to meet National

Safety Code Standards.If components are to be added to a unit

to meet local codes, they are to be installed at the dealer's

and/or the customer's expense.

LOCATION

Use the following guidelines to select a suitable location for

these units.

1. The outdoor units must be installed outside the building.

The outdoor fans are the propeller type and are not suitable

for use with duct work.

2. The outdoor and indoor units should be installed as close

together as possible and with a minimum number of bends

in the refrigerant piping. Refer to REFRIGERANT PIPING

for additional information.

3. The outdoor unit should not be installed beneath windows

or between structures where normal operating sounds may

be objectionable.

WARNING: The outdoor unit should not be installed in an area

where mud and/or ice could cause personal injury.

Remember that condensate will drip from the un-

derside of the unit coils during heat and defrost cy-

cles and that this condensate will freeze when the
temperature of the outdoor air is below 32

°

F.

4. All units require certain clearances for proper operation and

service. Refer to General Installation Form 55.70-N1 for

additional guidelines.

On either roof top or ground level installations, rubber padding

can be applied between the base rails and their supports to

lessen any transmission of vibration.

ROOF-TOP LOCATIONS

Be careful not to damagethe roof. Consultthe buildingcontrac-

tor or architectif the roof is bonded.Choosea locationwith ade-

quate structural strength to support the unit.
The unit must be mounted on solid level supports. The sup-

ports can be channel iron beams or wooden beams treated to

reduce deterioration.
A minimum of two (2) beams are required to support each unit.

The beams should: (1) Be positioned perpendicular to the roof

joists. (2) Extend beyond the dimensions of the unit to

distribute the load on the roof, (3) Be capable of adequately

supporting the entire unit weight. Refer to Figure 1 and Table 2

for load distribution and weights.
Thesebeamscan usuallybe set directlyon the roof. Flashingis

not required.

NOTE:

On bonded roofs, check for special installation re-

quirements.

GROUND LEVEL LOCATIONS

The units must be installed on a substantial base that will not

settle. Any strain on the refrigerant lines may cause a refriger-

ant leak. Aone-piececoncrete slab with footers that extend be-

low the frost line is recommended. The slab should not be tied

to the building foundationbecause noise and vibration will tele-

graph into the building.
A unit can also be supported by concrete piers. These piers

should: (1) extend below the frost line, (2) be located under the

unit's four corners and (3) be sized to carry the entire unit

weight. Refer to Figure 1 and Table 2 for the center of gravity

and unit weight.
A gravel bed or some other means of handling the condensate

that will drop from the underside of the unit coil during the heat-

ing and defrost cycles may have to be provided.

CAUTION: Care should be taken to protect the unit from tam-

pering and unauthorized persons from injury.

Screws on access panels will prevent casual tam-

pering. Additional safety precautions such as

fences around the unit or locking devices on the

panels may be advisable. Check local authorities

for safety regulations.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any pack-

aging until the unit is near the place of installation.
Rig the unit by attaching nylon straps with hooks to the lifting

holes provided in the base rails. Spreaders, whose length ex-

ceeds the largest dimension across the unit, MUST be used

across the top of the unit if the rigging height above the top of

the unit is less than 5 feet. See Figure 2.

WARNING: Do not use straps under the unit or through the fork

lift slots for lifting purposes. Sharp metal edges

can damage the straps and could result in per-

sonal injury or equipment damage.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT

IS DISTRIBUTED EQUALLY ON THE STRAPS SO THAT IT

WILL LIFT EVENLY.

Unitary Products Group

3

035-15410-002-B-0404

INSTALLATION

Voltage Variation (Min/Max.)

1

208/230-3-60

460-3-60

380/415-3-50

187/252

432/504

342/456

Air Temperature on OUTDOOR coil,

°

F

Minimum

Maximum

Cool

Heat

Cool

Heat

40db

0db

2

115db

75db

Air Temperature on INDOOR coil,

°

F

Minimum

Maximum

Cool

Heat

Cool

Heat

57wb

50db

3

72wb

80db

Maximum Line Lengths - 125 ft.

1

Rated in accordance with ARI Standard 110, utilization range “A”.

2

Below 0

°

F, the control system stops the compressor and allows the electric heat accessory to

cycle at its standby capacity.

3

Operation below this temperature is permissible for a short period of time when a unit is

required to heat the conditioned space up to 50

°

F.

TABLE 1

- UNIT APPLICATION DATA

FRONT

APPROXIMATE

CENTER OF GRAVITY

BACK

(COIL

END)

A

C

D

B

Unit

Dim. (Iin.)

A

B

C

D

7-1/2 Ton

42-3/4

31-3/4

21-1/4

11-1/2

10 Ton

70-1/8

32

30-3/4

15-1/8

FIG. 1

- CENTER OF GRAVITY

Summary of Contents for E2FB120

Page 1: ...elistingof replacementparts on this equipment The above forms may be ordered from Standard Register TOLL FREE Telephone 877 318 9675 TOLL FREE Fax 877 379 7920 Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert the installer thatperso...

Page 2: ... Sizing 7 Service Valves 8 EXTENDING THE SERVICE PORTS 8 INSTALLATION 8 EVACUATING AND CHARGING 9 BALANCE POINT SETTING 10 OPERATION GENERAL 13 SYSTEM SEQUENCE OF OPERATION Cooling Operation 13 Heating Operation 13 Defrost Cycle 14 Operation Below 0 F 14 Emergency Heat Operation 14 START UP CRANKCASE HEATER 10 Ton Unit Only 15 PRE START CHECK 15 INITIAL START UP 15 SAFETY FEATURES 15 SECURE OWNER ...

Page 3: ...ll not settle Any strain on the refrigerantlines may cause a refriger antleak Aone piececoncreteslabwithfootersthatextendbe low the frost line is recommended The slab should not be tied tothebuildingfoundationbecausenoiseandvibrationwilltele graph into the building A unit can also be supported by concrete piers These piers should 1 extendbelowthefrostline 2 be locatedunderthe unit s four corners a...

Page 4: ...ck the size of the power wire the discon nect switch and the fuses against the data on Table 3 NOTE Copperconductorsmustbeinstalledbetweenthedis connectswitch and the unit Refer to Figure 4 for the location of the power wire access openingthroughthefrontoftheunit Thisopeningwillrequirea field supplied conduit fitting The field supplied disconnect switch must be suitable for an outdoor location Alt...

Page 5: ...ly Qty FLA Each E3FB 090A 25 200 230 3 60 25 6 180 0 0 94 208V 208 230 1 60 1 3 03 35 1 60 0 84 230V 46 460 3 60 13 5 95 0 0 86 460 1 60 1 1 6 18 4 30 50 308 415 3 50 13 5 85 0 0 86 380V 380 415 1 50 1 1 6 18 4 30 0 79 415V E2FB 120A 25 208 230 3 60 42 0 239 0 0 91 208V 208 230 1 60 2 2 7 51 8 70 0 82 230V 46 460 3 60 19 2 125 0 0 82 460 1 60 2 1 6 24 7 35 50 380 415 3 50 19 6 118 0 0 87 380V 380 ...

Page 6: ...out notice Certified dimensions will be provided upon request CLEARANCES Overhead Top 1 120 Front Piping and Access Panels 30 Left Side 24 Right Side 24 Rear K 24 Bottom 2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct air discharge outlet 2 Adequate snow clearance must be provided if winter operation is expected ...

Page 7: ... cooling and heating cycles Friction loss should always be based on cooling operation be cause refrigerant flow rates will be greater during the cooling cycle than during the heating cycle Oil return will be critical during 1 The cooling cycle when the outdoor unit is above the indoor unit detail 1 of Figure 5 2 The heating cycle when the indoor unit is above the outdoor unit detail 4 of Figure 5 ...

Page 8: ...n recovered and that the liquid service valve on the unit is front seated and closed The valve stem should be turned to its maxi mum clockwise position 2 Drill a small hole through the disc before unbrazing it to per mit a flow of dry nitrogen through the connection while it is being unbrazed WARNING This hole is also required to prevent the internal pressure from building up as the disc is being ...

Page 9: ... service valve and the hole in the vapor disc 5 After the disc has been removed burnish the external sur faces and clean the internal surfaces of the vapor connec tion and the vapor piping The vapor line can now be brazed to the vapor connection on the outdoor unit while maintaining the flow of dry nitrogen Aftertheliquidandvaporlineshavebeeninstalled thesystem should be evacuated and charged EVAC...

Page 10: ...1 The outdoor design temperature 2 The building heat loss at the outdoor design temperature and 3 The heating capacity of the system at the outdoor design temperature Refer to Form 515 41 AD1 to determine balance point Referto 035 05163 001 for details regardingthe outdooram bient balance point control accessory Model No 2BP11700224 10 Unitary Products Group 035 15410 002 B 0404 FIG 6 EXTENDING TH...

Page 11: ...Unitary Products Group 11 035 15410 002 B 0404 FIG 7 REFRIGERANT FLOW DIAGRAM ...

Page 12: ...035 15410 002 B 0404 12 Unitary Products Group FIG 8 CHARGING CURVE EFB090 FIG 9 CHARGING CURVE EFB120 ...

Page 13: ... temperature reaches 255 F 2TH thermostat will open and the defrost control board will lock out the compressor If the suction pressure falls to 7 psig the low pressure switch will open and the defrost control will lock out the compressor 8 If the control that caused the lockout has automatically re set the unit can be restarted by one of the following a Turning the system switch on the thermostat ...

Page 14: ... defrost cycle will be terminated when a the liquid temperature exceeds 55 F or b 10 minutes have passed since defrost initiation The 10 minute cycle time independent of liquid line tem perature is controlled by the defrost control board 4 At defrost termination the unit returns to the normal heat ing operation OPERATION BELOW 0 F OUTDOOR TEMPERATURE 1 At 0 F outdoor temperature the low temperatur...

Page 15: ...or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been operating for several minutes shut off the main power supply at the disconnect switch and in spect all factory wiring connections and bolted surfaces for tightness SAFETY FEATURES 1 All outdoor fan motors have inherent protection with auto...

Page 16: ...s Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright 2004 by York International Corporation All Rights Reserved 035 15410 002 B 0404 Supersedes 035 15410 002 A 0304 ...

Reviews: