background image

Use hard drawn copper tubing where no appreciableamountof

bending around pipes or other obstructions is necessary. Use

long radius ells wherever possible with one exception - small

radius ells for the traps in all vapor risers. If soft copper is used,

care should be taken to avoid sharp bends which may cause a

restriction.

Pack fiber glass insulation and a sealing material such as

Permagum around refrigerant lines where they penetrate a

wall to reduce vibration and to retain some flexibility.

Support all refrigerant lines at minimum intervals with suitable

hangers, brackets or clamps.
Braze all copper to copper joints with Silfos-5 or equivalent

brazing material. Do not use soft solder.
Insulate all vapor lines with a minimum of 1/2" ARMA-FLEX or

equal. Liquid lines exposed to direct sunlight and/or high tem-

peratures must also be insulated.
Never solder vapor and liquid lines together. They can be taped

together for convenience and support purposes, but they must

be completely insulated from each other.
Never exceed the maximum line length listed in Table 1.

LINE SIZING

The following factors should be considered when locating the

indoor and outdoor units and when sizing the refrigerant lines

for a split heat pump system. Refer to Figure 5.

THE LIQUID LINE - The vertical rise should never exceed 50

feet because liquid refrigerant will lose 0.5 psi of static head for

each vertical foot.
The total pressure loss for a field-installed liquid line should

never exceed 40 psi because the liquid refrigerant could flash

before it reaches the expansion valve. This flashing will not

only cause erratic valve operation and poor system perform-

ance, but could also damage the expansion valve.
Total pressure loss includes the static head loss explained

above plus the friction losses due to the length of the line (Table

4) and number of fittings in the line.
When the indoor unit is above the outdoor unit, the friction loss

through the 1-1/8" OD vapor riser will be more of a limiting fac-

tor than the loss of static head in the liquid riser. See Example

#3 and #4 for the VAPOR LINE.

THE VAPOR LINE - A vapor line should not only be sized for a

friction loss of 3 psi (2

°

F) but also for the proper return of oil to

the compressor during both the cooling and heating cycles.

Friction loss should always be based on cooling operation be-

cause refrigerant flow rates will be greater during the cooling

cycle than during the heating cycle.

Oil return will be critical during:

1.

The cooling cycle when the outdoor unit is above the indoor

unit (detail 1 of Figure 5).

2.

The heating cycle when the indoor unit is above the outdoor

unit (detail 4 of Figure 5).

When the indoor unit is above the outdoor unit, the size of the

vapor riser must be reduced to 1-1/8" OD so that the velocity of

the refrigerant will be great enough to carry oil up the riser dur-

ing the heating cycle.
When 1-1/8" OD tubing must be used for the riser, the maxi-

mum length for the vapor line will be greatly reduced as shown

in the following examples.

EXAMPLES:
#1 - 7-1/2 Ton System

125 feet of 1-3/8" OD, type “L” copper tubing

(125 feet x 1.6 psi/100 feet) ...........................................2.0 psi

Fitting*....................................................................................0.4 psi

Vapor Line Pressure Drop = 2.4 psi

#2 - 10 Ton System

89 feet of 1-3/8" OD, type “L” copper tubing

(89 feet x 2.8 psi/100 feet) .............................................2.5 psi

Fitting*....................................................................................0.5 psi

Vapor Line Pressure Drop = 3.0 psi

#3 - 7-1/2 Ton System

51 feet of 1-1/8" OD, type “L” copper tubing (vertical)

(51 feet x 4.7 psi/100 feet) .............................................2.4 psi

6 feet of 1-3/8" OD, type “L” copper tubing (horizontal)

(6 feet x 1.6 psi/100 feet) ...............................................0.1 psi

Fitting*....................................................................................0.5 psi

Vapor Line Pressure Drop = 3.0 psi

#4 - 10 Ton System

29 feet of 1-1/8" OD, type “L” copper tubing (vertical)

Unitary Products Group

7

035-15410-002-B-0404

System

Model

Refrigerant

Flow Rate,

1

(Lbs/Min)

Type “L”

Copper

Tubing,

(In. OD)

Pressure Drop

3

Friction,

2

(PSI/100 Ft)

Vertical

Rise

(PSI/Ft)

EFB090/FEH090

22.5

5/8

3.5

0.5

EFB120/FEH120

30.0

5/8

5.8

0.5

1

Based on Refrigerant-22 at the nominal cooling capacity of the system, a liquid temperature

of 105

°

F and a vapor temperature of 40

°

F. Since refrigerant flow rates will be a little lower at

the nominal heating capacity of each system, liquid line friction loss should always be based

on cooling operation.

2

These friction losses do not include any allowance for fittings.

3

The total pressure drop of the liquid line for both friction and vertical rise must not exceed 40

PSI. If the pressure drop exceeds 40 PSI, the liquid refrigerant could flash before it reaches

the expansion valve. This flashing will not only cause erratic valve operation and poor system

performance, but could also damage the expansion valve.

TABLE 4

- LIQUID LINES

FIG. 5

- FIELD PIPING DIAGRAMS

(Cooling/Heating Refrigerant Flow)

Summary of Contents for E2FB120

Page 1: ...elistingof replacementparts on this equipment The above forms may be ordered from Standard Register TOLL FREE Telephone 877 318 9675 TOLL FREE Fax 877 379 7920 Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert the installer thatperso...

Page 2: ... Sizing 7 Service Valves 8 EXTENDING THE SERVICE PORTS 8 INSTALLATION 8 EVACUATING AND CHARGING 9 BALANCE POINT SETTING 10 OPERATION GENERAL 13 SYSTEM SEQUENCE OF OPERATION Cooling Operation 13 Heating Operation 13 Defrost Cycle 14 Operation Below 0 F 14 Emergency Heat Operation 14 START UP CRANKCASE HEATER 10 Ton Unit Only 15 PRE START CHECK 15 INITIAL START UP 15 SAFETY FEATURES 15 SECURE OWNER ...

Page 3: ...ll not settle Any strain on the refrigerantlines may cause a refriger antleak Aone piececoncreteslabwithfootersthatextendbe low the frost line is recommended The slab should not be tied tothebuildingfoundationbecausenoiseandvibrationwilltele graph into the building A unit can also be supported by concrete piers These piers should 1 extendbelowthefrostline 2 be locatedunderthe unit s four corners a...

Page 4: ...ck the size of the power wire the discon nect switch and the fuses against the data on Table 3 NOTE Copperconductorsmustbeinstalledbetweenthedis connectswitch and the unit Refer to Figure 4 for the location of the power wire access openingthroughthefrontoftheunit Thisopeningwillrequirea field supplied conduit fitting The field supplied disconnect switch must be suitable for an outdoor location Alt...

Page 5: ...ly Qty FLA Each E3FB 090A 25 200 230 3 60 25 6 180 0 0 94 208V 208 230 1 60 1 3 03 35 1 60 0 84 230V 46 460 3 60 13 5 95 0 0 86 460 1 60 1 1 6 18 4 30 50 308 415 3 50 13 5 85 0 0 86 380V 380 415 1 50 1 1 6 18 4 30 0 79 415V E2FB 120A 25 208 230 3 60 42 0 239 0 0 91 208V 208 230 1 60 2 2 7 51 8 70 0 82 230V 46 460 3 60 19 2 125 0 0 82 460 1 60 2 1 6 24 7 35 50 380 415 3 50 19 6 118 0 0 87 380V 380 ...

Page 6: ...out notice Certified dimensions will be provided upon request CLEARANCES Overhead Top 1 120 Front Piping and Access Panels 30 Left Side 24 Right Side 24 Rear K 24 Bottom 2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct air discharge outlet 2 Adequate snow clearance must be provided if winter operation is expected ...

Page 7: ... cooling and heating cycles Friction loss should always be based on cooling operation be cause refrigerant flow rates will be greater during the cooling cycle than during the heating cycle Oil return will be critical during 1 The cooling cycle when the outdoor unit is above the indoor unit detail 1 of Figure 5 2 The heating cycle when the indoor unit is above the outdoor unit detail 4 of Figure 5 ...

Page 8: ...n recovered and that the liquid service valve on the unit is front seated and closed The valve stem should be turned to its maxi mum clockwise position 2 Drill a small hole through the disc before unbrazing it to per mit a flow of dry nitrogen through the connection while it is being unbrazed WARNING This hole is also required to prevent the internal pressure from building up as the disc is being ...

Page 9: ... service valve and the hole in the vapor disc 5 After the disc has been removed burnish the external sur faces and clean the internal surfaces of the vapor connec tion and the vapor piping The vapor line can now be brazed to the vapor connection on the outdoor unit while maintaining the flow of dry nitrogen Aftertheliquidandvaporlineshavebeeninstalled thesystem should be evacuated and charged EVAC...

Page 10: ...1 The outdoor design temperature 2 The building heat loss at the outdoor design temperature and 3 The heating capacity of the system at the outdoor design temperature Refer to Form 515 41 AD1 to determine balance point Referto 035 05163 001 for details regardingthe outdooram bient balance point control accessory Model No 2BP11700224 10 Unitary Products Group 035 15410 002 B 0404 FIG 6 EXTENDING TH...

Page 11: ...Unitary Products Group 11 035 15410 002 B 0404 FIG 7 REFRIGERANT FLOW DIAGRAM ...

Page 12: ...035 15410 002 B 0404 12 Unitary Products Group FIG 8 CHARGING CURVE EFB090 FIG 9 CHARGING CURVE EFB120 ...

Page 13: ... temperature reaches 255 F 2TH thermostat will open and the defrost control board will lock out the compressor If the suction pressure falls to 7 psig the low pressure switch will open and the defrost control will lock out the compressor 8 If the control that caused the lockout has automatically re set the unit can be restarted by one of the following a Turning the system switch on the thermostat ...

Page 14: ... defrost cycle will be terminated when a the liquid temperature exceeds 55 F or b 10 minutes have passed since defrost initiation The 10 minute cycle time independent of liquid line tem perature is controlled by the defrost control board 4 At defrost termination the unit returns to the normal heat ing operation OPERATION BELOW 0 F OUTDOOR TEMPERATURE 1 At 0 F outdoor temperature the low temperatur...

Page 15: ...or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been operating for several minutes shut off the main power supply at the disconnect switch and in spect all factory wiring connections and bolted surfaces for tightness SAFETY FEATURES 1 All outdoor fan motors have inherent protection with auto...

Page 16: ...s Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright 2004 by York International Corporation All Rights Reserved 035 15410 002 B 0404 Supersedes 035 15410 002 A 0304 ...

Reviews: