background image

IN ALL THREE RESET METHODS DESCRIBED ABOVE,

A FIVE MINUTE TIME DELAY WILL TAKE PLACE AFTER

THE RESET BEFORE THE UNIT WILL RESTART.

8. Supplemental electric heat (if installed) will be controlled by

second stage TH2 of the thermostat. The supplemental
electric heat circuit is controlled through low voltage termi-
nals W, 60 and 66. The standby portion of electric heat
(controlled through low voltage terminal 53) cannot operate
because relay 4R is energized, opening the circuit to termi-
nal 53, whenever the compressor is operating.

9. When second stage heating TH2 is satisfied, the supple-

mental heaters will be de-energized.

DEFROST CYCLE

When condensate freezes on the outdoor coil during heating

operation, it must be defrosted before it blocks the flow of air

across the coil.

1. A defrost cycle will be initiated by the defrost control board's

timed defrost feature.

2. When the defrost cycle is initiated, the unit operates as fol-

lows:

a. The reversing valve solenoid is energized through the

defrost control board causing the unit to switch to the

cooling cycle.

b. Defrost control board de-energizes 2M contactor, caus-

ing the outdoor section fan(s) to shut down.

c. Supplemental electric heat (if installed) will be ener-

gized through defrost control board. Only that portion of

electric heat controlled through low voltage control ter-

minal 66 will be energized by the defrost cycle. The op-

eration of supplemental electric heat during unit defrost

will prevent cold drafts in the conditioned space.

3. The defrost cycle will be terminated when:

a.  the liquid temperature exceeds 55

°

F, or

b. 10 minutes have passed since defrost initiation.

The 10 minute cycle time (independent of liquid line tem-

perature) is controlled by the defrost control board.

4. At defrost termination, the unit returns to the normal heat-

ing operation.

OPERATION BELOW 0

°

F OUTDOOR

TEMPERATURE

1. At 0

°

F outdoor temperature, the low temperature compres-

sor cutoff thermostat 1TH contacts 1 and 3 will open, de-

energizing contactor 1M which shuts down the compres-

sor. Contacts 1 and 2 of thermostat 1TH are closed when

contacts 1 and 3 are open. This feature allows the standby

electric heat (if installed) to operate under control of first

stage heating TH1 of the room thermostat whenever the

compressor is shut-down by the 1TH control. The supple-

mental electric heat will continue to be controlled by the

second stage TH2 of the room thermostat same as de-

scribed under Item 8 of HEATING OPERATION.

2. The indoor section blower operation will be controlled by

the first stage heating TH1 of the room thermostat if the fan

switch is in the “AUTO” position.

EMERGENCY HEAT OPERATION

When the system switch on the room thermostat is placed in

the EMERGENCY HEAT position, operation is as follows:

1. The emergency heat light on the room thermostat will be

energized.

2. Compressor will not operate because the Y circuit of the

room thermostat cannot be energized.

3. Supplemental and standby electric heat (if installed) will be

controlled by first stage heating TH1 of room thermostat.

4. Indoor section blower will also be controlled by first stage

heating TH1 if fan switch is in the “AUTO” position.

035-15410-002-B-0404

14

Unitary Products Group

Summary of Contents for E2FB120

Page 1: ...elistingof replacementparts on this equipment The above forms may be ordered from Standard Register TOLL FREE Telephone 877 318 9675 TOLL FREE Fax 877 379 7920 Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert the installer thatperso...

Page 2: ... Sizing 7 Service Valves 8 EXTENDING THE SERVICE PORTS 8 INSTALLATION 8 EVACUATING AND CHARGING 9 BALANCE POINT SETTING 10 OPERATION GENERAL 13 SYSTEM SEQUENCE OF OPERATION Cooling Operation 13 Heating Operation 13 Defrost Cycle 14 Operation Below 0 F 14 Emergency Heat Operation 14 START UP CRANKCASE HEATER 10 Ton Unit Only 15 PRE START CHECK 15 INITIAL START UP 15 SAFETY FEATURES 15 SECURE OWNER ...

Page 3: ...ll not settle Any strain on the refrigerantlines may cause a refriger antleak Aone piececoncreteslabwithfootersthatextendbe low the frost line is recommended The slab should not be tied tothebuildingfoundationbecausenoiseandvibrationwilltele graph into the building A unit can also be supported by concrete piers These piers should 1 extendbelowthefrostline 2 be locatedunderthe unit s four corners a...

Page 4: ...ck the size of the power wire the discon nect switch and the fuses against the data on Table 3 NOTE Copperconductorsmustbeinstalledbetweenthedis connectswitch and the unit Refer to Figure 4 for the location of the power wire access openingthroughthefrontoftheunit Thisopeningwillrequirea field supplied conduit fitting The field supplied disconnect switch must be suitable for an outdoor location Alt...

Page 5: ...ly Qty FLA Each E3FB 090A 25 200 230 3 60 25 6 180 0 0 94 208V 208 230 1 60 1 3 03 35 1 60 0 84 230V 46 460 3 60 13 5 95 0 0 86 460 1 60 1 1 6 18 4 30 50 308 415 3 50 13 5 85 0 0 86 380V 380 415 1 50 1 1 6 18 4 30 0 79 415V E2FB 120A 25 208 230 3 60 42 0 239 0 0 91 208V 208 230 1 60 2 2 7 51 8 70 0 82 230V 46 460 3 60 19 2 125 0 0 82 460 1 60 2 1 6 24 7 35 50 380 415 3 50 19 6 118 0 0 87 380V 380 ...

Page 6: ...out notice Certified dimensions will be provided upon request CLEARANCES Overhead Top 1 120 Front Piping and Access Panels 30 Left Side 24 Right Side 24 Rear K 24 Bottom 2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct air discharge outlet 2 Adequate snow clearance must be provided if winter operation is expected ...

Page 7: ... cooling and heating cycles Friction loss should always be based on cooling operation be cause refrigerant flow rates will be greater during the cooling cycle than during the heating cycle Oil return will be critical during 1 The cooling cycle when the outdoor unit is above the indoor unit detail 1 of Figure 5 2 The heating cycle when the indoor unit is above the outdoor unit detail 4 of Figure 5 ...

Page 8: ...n recovered and that the liquid service valve on the unit is front seated and closed The valve stem should be turned to its maxi mum clockwise position 2 Drill a small hole through the disc before unbrazing it to per mit a flow of dry nitrogen through the connection while it is being unbrazed WARNING This hole is also required to prevent the internal pressure from building up as the disc is being ...

Page 9: ... service valve and the hole in the vapor disc 5 After the disc has been removed burnish the external sur faces and clean the internal surfaces of the vapor connec tion and the vapor piping The vapor line can now be brazed to the vapor connection on the outdoor unit while maintaining the flow of dry nitrogen Aftertheliquidandvaporlineshavebeeninstalled thesystem should be evacuated and charged EVAC...

Page 10: ...1 The outdoor design temperature 2 The building heat loss at the outdoor design temperature and 3 The heating capacity of the system at the outdoor design temperature Refer to Form 515 41 AD1 to determine balance point Referto 035 05163 001 for details regardingthe outdooram bient balance point control accessory Model No 2BP11700224 10 Unitary Products Group 035 15410 002 B 0404 FIG 6 EXTENDING TH...

Page 11: ...Unitary Products Group 11 035 15410 002 B 0404 FIG 7 REFRIGERANT FLOW DIAGRAM ...

Page 12: ...035 15410 002 B 0404 12 Unitary Products Group FIG 8 CHARGING CURVE EFB090 FIG 9 CHARGING CURVE EFB120 ...

Page 13: ... temperature reaches 255 F 2TH thermostat will open and the defrost control board will lock out the compressor If the suction pressure falls to 7 psig the low pressure switch will open and the defrost control will lock out the compressor 8 If the control that caused the lockout has automatically re set the unit can be restarted by one of the following a Turning the system switch on the thermostat ...

Page 14: ... defrost cycle will be terminated when a the liquid temperature exceeds 55 F or b 10 minutes have passed since defrost initiation The 10 minute cycle time independent of liquid line tem perature is controlled by the defrost control board 4 At defrost termination the unit returns to the normal heat ing operation OPERATION BELOW 0 F OUTDOOR TEMPERATURE 1 At 0 F outdoor temperature the low temperatur...

Page 15: ...or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been operating for several minutes shut off the main power supply at the disconnect switch and in spect all factory wiring connections and bolted surfaces for tightness SAFETY FEATURES 1 All outdoor fan motors have inherent protection with auto...

Page 16: ...s Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright 2004 by York International Corporation All Rights Reserved 035 15410 002 B 0404 Supersedes 035 15410 002 A 0304 ...

Reviews: