background image

Units may also be moved or lifted with a fork-lift. Slotted open-

ings in the base rails are provided for this purpose. The 7-1/2

ton unit may be lifted from either the LH or RH side - under the

unit.
LENGTH OF FORKS MUST BE A MINIMUM OF 42" (for 7-1/2

ton units) and a MINIMUM OF 54" (for 10 ton units) when lifting

from either side.
Remove the nesting brackets from the four corners on top of

the unit. All screws that are removed to take these brackets off

must be replaced on the unit

CLEARANCES

All units require certain minimum clearances for proper opera-

tion and service. Refer to Figure 4 for these clearances.

WARNING: Do not permit overhanging structures or shrubs to

obstruct air discharge.

Additional height may be required for snow clearance if winter

operation is expected.

COMPRESSORS

Units are shippedwith compressormountingsfactory-adjusted

and ready for operation.

CAUTION: Do Not loosen compressor mounting bolts.

COMPRESSOR CRANKCASE HEATER

The compressor is equipped with a crankcase heater to pre-

vent refrigerant from mixing with crankcase oil during the

“OFF” cycle. The heaters will be energized when the compres-

sor is not running providing the unit disconnect switch is

closed.

CAUTION: Do not attempt to start the compressor without at

least eight hours of crankcase heat or compressor

damage will occur.

If a unit has just been installed or the unit disconnect switch has

been open for a long period of time, move the system switch on

the room thermostat to the “OFF” position before closing the

unit disconnect switch. Eight hours of crankcase heat are re-

quired to drive the liquid refrigerant out of the compressor bef-

ore the compressor can be started.

POWER AND CONTROL WIRING

Install electrical wiring in accordance with the latest National

Electrical Code (NFPA Standard No. 70) and/or local regula-

tions. The unit should be grounded in accordance with these

codes.

POWER WIRING

Check the voltage of the power supply against the data on the

unit nameplate. Check the size of the power wire, the discon-

nect switch and the fuses against the data on Table 3.

NOTE:

Copper conductors must be installed between the dis-

connect switch and the unit.

Refer to Figure 4 for the location of the power wire access

opening through the front of the unit. This opening will require a

field-supplied conduit fitting.

The field-supplied disconnect switch must be suitable for an

outdoor location. Although it should be installed near the unit,

do NOT secure it to the unit cabinet.

Refer to Figure 3 for typical field wiring.

CONTROL WIRING

Refer to Figure 4 for the location of the control wire access

opening through the front of the unit.

Route the necessary low voltage control wires from terminal

block 1TB of the unit controlbox throughthis accessopeningto

the indoor unit and to the room thermostat. Refer to Figure 3 for

typical field wiring.

The room thermostat should be mounted about 5 feet above

the floor and located where it will be exposed to normal room

air circulation.Do not locate it on an outside wall, near a supply

air grill, or where it may be affected by sunlight and/or drafts.

Circulation of air to the thermostat should not be blocked by

curtains, drapes, furniture, partitions, etc.

4

Unitary Products Group

035-15410-002-B-0404

FIG. 2

- TYPICAL RIGGING

MODEL

EFB090

EFB120

Compressor

1

Rating, (Tons)

7-1/2

10

Fans

Quantity

1

2

Diameter, (In.)/No. Blades

24/3

24/3

Nominal CFM

4604

7600

Fan Motors

2

HP

3/4

1/2

RPM

1100

1100

Coil

Face Area, (Sq. Ft.)

18.75

24.00

Rows Deep x Rows High

2 x 30

2 x 36

Finned Length, (In.)

90

96

Tube (Copper) OD - inches

3/8

3/8

Fins (Aluminum) per inch

18

16

Refrigerant-22

(Lbs.)

Holding Charge

1.0

2.25

Operating Charge

3

14.3

21.4

Pumpdown Capacity

4

19.6

24.6

Unit Weight

(Lbs.)

Shipping

355

435

Operating

350

430

1

These compressors are fully hermetic.

2

These PSC motors are directly connected to the outdoor fans and have inherent protection,

ball bearings and a 48 frame. Rotation (when viewing the shaft end of the motor) - 090=CW,

120=CCW.

3

Includes outdoor unit and matched indoor blower unit, but no piping. Refer to Table 6 for re-

frigerant line charge.

4

Based on a 95

°

F ambient.

TABLE 2

- PHYSICAL DATA

5   F T .   M I N .

FORK-LIFT

OPENINGS

7-1/2 TON UNIT SHOWN

Summary of Contents for E2FB120

Page 1: ...elistingof replacementparts on this equipment The above forms may be ordered from Standard Register TOLL FREE Telephone 877 318 9675 TOLL FREE Fax 877 379 7920 Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert the installer thatperso...

Page 2: ... Sizing 7 Service Valves 8 EXTENDING THE SERVICE PORTS 8 INSTALLATION 8 EVACUATING AND CHARGING 9 BALANCE POINT SETTING 10 OPERATION GENERAL 13 SYSTEM SEQUENCE OF OPERATION Cooling Operation 13 Heating Operation 13 Defrost Cycle 14 Operation Below 0 F 14 Emergency Heat Operation 14 START UP CRANKCASE HEATER 10 Ton Unit Only 15 PRE START CHECK 15 INITIAL START UP 15 SAFETY FEATURES 15 SECURE OWNER ...

Page 3: ...ll not settle Any strain on the refrigerantlines may cause a refriger antleak Aone piececoncreteslabwithfootersthatextendbe low the frost line is recommended The slab should not be tied tothebuildingfoundationbecausenoiseandvibrationwilltele graph into the building A unit can also be supported by concrete piers These piers should 1 extendbelowthefrostline 2 be locatedunderthe unit s four corners a...

Page 4: ...ck the size of the power wire the discon nect switch and the fuses against the data on Table 3 NOTE Copperconductorsmustbeinstalledbetweenthedis connectswitch and the unit Refer to Figure 4 for the location of the power wire access openingthroughthefrontoftheunit Thisopeningwillrequirea field supplied conduit fitting The field supplied disconnect switch must be suitable for an outdoor location Alt...

Page 5: ...ly Qty FLA Each E3FB 090A 25 200 230 3 60 25 6 180 0 0 94 208V 208 230 1 60 1 3 03 35 1 60 0 84 230V 46 460 3 60 13 5 95 0 0 86 460 1 60 1 1 6 18 4 30 50 308 415 3 50 13 5 85 0 0 86 380V 380 415 1 50 1 1 6 18 4 30 0 79 415V E2FB 120A 25 208 230 3 60 42 0 239 0 0 91 208V 208 230 1 60 2 2 7 51 8 70 0 82 230V 46 460 3 60 19 2 125 0 0 82 460 1 60 2 1 6 24 7 35 50 380 415 3 50 19 6 118 0 0 87 380V 380 ...

Page 6: ...out notice Certified dimensions will be provided upon request CLEARANCES Overhead Top 1 120 Front Piping and Access Panels 30 Left Side 24 Right Side 24 Rear K 24 Bottom 2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct air discharge outlet 2 Adequate snow clearance must be provided if winter operation is expected ...

Page 7: ... cooling and heating cycles Friction loss should always be based on cooling operation be cause refrigerant flow rates will be greater during the cooling cycle than during the heating cycle Oil return will be critical during 1 The cooling cycle when the outdoor unit is above the indoor unit detail 1 of Figure 5 2 The heating cycle when the indoor unit is above the outdoor unit detail 4 of Figure 5 ...

Page 8: ...n recovered and that the liquid service valve on the unit is front seated and closed The valve stem should be turned to its maxi mum clockwise position 2 Drill a small hole through the disc before unbrazing it to per mit a flow of dry nitrogen through the connection while it is being unbrazed WARNING This hole is also required to prevent the internal pressure from building up as the disc is being ...

Page 9: ... service valve and the hole in the vapor disc 5 After the disc has been removed burnish the external sur faces and clean the internal surfaces of the vapor connec tion and the vapor piping The vapor line can now be brazed to the vapor connection on the outdoor unit while maintaining the flow of dry nitrogen Aftertheliquidandvaporlineshavebeeninstalled thesystem should be evacuated and charged EVAC...

Page 10: ...1 The outdoor design temperature 2 The building heat loss at the outdoor design temperature and 3 The heating capacity of the system at the outdoor design temperature Refer to Form 515 41 AD1 to determine balance point Referto 035 05163 001 for details regardingthe outdooram bient balance point control accessory Model No 2BP11700224 10 Unitary Products Group 035 15410 002 B 0404 FIG 6 EXTENDING TH...

Page 11: ...Unitary Products Group 11 035 15410 002 B 0404 FIG 7 REFRIGERANT FLOW DIAGRAM ...

Page 12: ...035 15410 002 B 0404 12 Unitary Products Group FIG 8 CHARGING CURVE EFB090 FIG 9 CHARGING CURVE EFB120 ...

Page 13: ... temperature reaches 255 F 2TH thermostat will open and the defrost control board will lock out the compressor If the suction pressure falls to 7 psig the low pressure switch will open and the defrost control will lock out the compressor 8 If the control that caused the lockout has automatically re set the unit can be restarted by one of the following a Turning the system switch on the thermostat ...

Page 14: ... defrost cycle will be terminated when a the liquid temperature exceeds 55 F or b 10 minutes have passed since defrost initiation The 10 minute cycle time independent of liquid line tem perature is controlled by the defrost control board 4 At defrost termination the unit returns to the normal heat ing operation OPERATION BELOW 0 F OUTDOOR TEMPERATURE 1 At 0 F outdoor temperature the low temperatur...

Page 15: ...or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been operating for several minutes shut off the main power supply at the disconnect switch and in spect all factory wiring connections and bolted surfaces for tightness SAFETY FEATURES 1 All outdoor fan motors have inherent protection with auto...

Page 16: ...s Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright 2004 by York International Corporation All Rights Reserved 035 15410 002 B 0404 Supersedes 035 15410 002 A 0304 ...

Reviews: