background image

CRANKCASE HEATER

The crankcase heaters must be energized at least 8 hours bef-

ore starting the compressor. To energize the crankcase heat-

ers, the main disconnect switch must be closed. During this 8

hour period, the system switch on the room thermostat must be

“OFF” to prevent the compressor from starting.

CAUTION: DO NOT ATTEMPT TO START THE COMPRES-

SOR WITHOUT AT LEAST 8 HOURS OF

CRANKCASE HEAT OR COMPRESSOR DAM-

AGE WILL OCCUR.

Make sure that the bottom of the compressor is warm to the

touch to prove crankcase heater operation.

PRE-START CHECK

Before starting the unit, complete the following check list:

1. Have sufficient clearances been provided?
2. Has all foreign matter been removed from the interior of the

unit (tools, construction or shipping materials, etc.)?

3. Have the outdoor fans been rotated manually to check for

free rotation?

4. Are all wiring connections tight?
5. Does the available power supply agree with the nameplate

data on the unit?

6. Have the fuses, disconnect switch and power wire been

sized properly?

7. Are all compressor hold-down nuts properly secured?
8. Are any refrigerant lines touching each other or any sheet

metal surface? Rubbing due to vibration could cause a re-

frigerant leak.

9. Are there any visible signs of a refrigerant leak, such as oil

residue?

10. Is any electrical wire laying against a hot refrigerant line?

Keep in mind that this unit has a reverse cycle and that dif-

ferent lines will be hot during the “HEAT” and “COOL” cy-

cles. Only two lines will remain cool for all cycles - the line

between the compressor and the accumulator and the line

between the accumulator and the reversing valve.

INITIAL START-UP

1. Supply power to the unit through the disconnect switch

prior to starting the compressor.

2. Move the system switch on the room thermostat to the

“COOL” position, and lower its set point to energize both

the compressor and the reversing valve. Cool air will be

supplied to the conditioned space.

Check the compressor amperage. It should not exceed

the RLA rating printed on the unit data plate or in Table 3

unless the ambient temperature is above 105

°

F.

4. Move the system switch on the room thermostat to the

“HEAT” position, and increase the set point of the room

thermostat until heating is required. The compressor will

run, but the reversing valve will be de-energized. Warm air

will be supplied to the conditioned space.

5. Check the operation of the indoor unit per Form 515.41-N2.
6. Check the entire system for refrigerant leaks.
7. Check for any abnormal noises and/or vibrations, and make

the necessary adjustments to correct (e.g. fan blade touching

shroud, refrigerant lines hitting on sheet metal, etc.)

8. After the unit has been operating for several minutes, shut

off the main power supply at the disconnect switch and in-

spect all factory wiring connections and bolted surfaces for

tightness.

SAFETY FEATURES

1. All outdoor fan motors have inherent protection with auto-

matic reset.

2. Every compressor is internally protected against excessive

current and temperature by a line break motor protector that is

mounted inside the compressor housing and is connected

between each winding and the common terminal.
This motor protector will interrupt power to the compressor

if any of the following overload conditions occur:

a. primary single phasing

b. locked rotor

c. compressor overload

d. insufficient motor cooling
This type of motor protection works even with the contac-

tor welded closed.

3. Every compressor is protected by crankcase heaters to

prevent refrigerant from accumulating in the crankcases of

the compressor during an “OFF” cycle.

4. Outdoor fan motors and the secondary of the control trans-

former are grounded.

5. A fusible plug on the top of the suction line accumulator

serves as a high temperature/high pressure relief device.

035-15410-002-B-0404

Unitary Products Group

15

START-UP

CAUTION:

DO NOT ATTEMPT TO START THE COMPRESSOR

WITHOUT AT LEAST 8 HOURS OF CRANKCASE HEAT OR

COMPRESSOR DAMAGE WILL OCCUR.

CLEANING

Do not allow dirt to accumulateon the outdoorcoil. Clean the coil

with a brush or vacuum cleaner as often as necessary to assure

good system performance and efficient operation. If the coil is

extremely dirty, it may be necessary to use an industrial grade

detergent and a hose to clean the fin surface.

LUBRICATION

The outdoor fan motors are equipped with factory lubricated

and sealed ball bearings. They do not require any mainte-

nance.

REPLACEMENT PARTS

Contact your local UPG Distribution Center for replacement

compressors, fan motors, controls, etc.

NOTICE TO OWNER

If a lockout occurs, check the indoor filters and the outdoor coil

before calling a serviceman. If the filters are dirty, clean or re-

place them. If there is an accumulationof snow, leaves or debris

blocking the outdoor air coil, remove the blockage. Reset the

thermostat and wait 5 minutes. If the unit doesn't start, call a

serviceman.

MAINTENANCE

SECURE OWNER'S APPROVAL:

When the system is functioning properly, secure the owner's approval. Show

him the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit, how to adjust

temperature settings within the limitations of the system, how the defrost cycle is controlled and how the anti-cycle timer

operates.

3.

Summary of Contents for E2FB120

Page 1: ...elistingof replacementparts on this equipment The above forms may be ordered from Standard Register TOLL FREE Telephone 877 318 9675 TOLL FREE Fax 877 379 7920 Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert the installer thatperso...

Page 2: ... Sizing 7 Service Valves 8 EXTENDING THE SERVICE PORTS 8 INSTALLATION 8 EVACUATING AND CHARGING 9 BALANCE POINT SETTING 10 OPERATION GENERAL 13 SYSTEM SEQUENCE OF OPERATION Cooling Operation 13 Heating Operation 13 Defrost Cycle 14 Operation Below 0 F 14 Emergency Heat Operation 14 START UP CRANKCASE HEATER 10 Ton Unit Only 15 PRE START CHECK 15 INITIAL START UP 15 SAFETY FEATURES 15 SECURE OWNER ...

Page 3: ...ll not settle Any strain on the refrigerantlines may cause a refriger antleak Aone piececoncreteslabwithfootersthatextendbe low the frost line is recommended The slab should not be tied tothebuildingfoundationbecausenoiseandvibrationwilltele graph into the building A unit can also be supported by concrete piers These piers should 1 extendbelowthefrostline 2 be locatedunderthe unit s four corners a...

Page 4: ...ck the size of the power wire the discon nect switch and the fuses against the data on Table 3 NOTE Copperconductorsmustbeinstalledbetweenthedis connectswitch and the unit Refer to Figure 4 for the location of the power wire access openingthroughthefrontoftheunit Thisopeningwillrequirea field supplied conduit fitting The field supplied disconnect switch must be suitable for an outdoor location Alt...

Page 5: ...ly Qty FLA Each E3FB 090A 25 200 230 3 60 25 6 180 0 0 94 208V 208 230 1 60 1 3 03 35 1 60 0 84 230V 46 460 3 60 13 5 95 0 0 86 460 1 60 1 1 6 18 4 30 50 308 415 3 50 13 5 85 0 0 86 380V 380 415 1 50 1 1 6 18 4 30 0 79 415V E2FB 120A 25 208 230 3 60 42 0 239 0 0 91 208V 208 230 1 60 2 2 7 51 8 70 0 82 230V 46 460 3 60 19 2 125 0 0 82 460 1 60 2 1 6 24 7 35 50 380 415 3 50 19 6 118 0 0 87 380V 380 ...

Page 6: ...out notice Certified dimensions will be provided upon request CLEARANCES Overhead Top 1 120 Front Piping and Access Panels 30 Left Side 24 Right Side 24 Rear K 24 Bottom 2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct air discharge outlet 2 Adequate snow clearance must be provided if winter operation is expected ...

Page 7: ... cooling and heating cycles Friction loss should always be based on cooling operation be cause refrigerant flow rates will be greater during the cooling cycle than during the heating cycle Oil return will be critical during 1 The cooling cycle when the outdoor unit is above the indoor unit detail 1 of Figure 5 2 The heating cycle when the indoor unit is above the outdoor unit detail 4 of Figure 5 ...

Page 8: ...n recovered and that the liquid service valve on the unit is front seated and closed The valve stem should be turned to its maxi mum clockwise position 2 Drill a small hole through the disc before unbrazing it to per mit a flow of dry nitrogen through the connection while it is being unbrazed WARNING This hole is also required to prevent the internal pressure from building up as the disc is being ...

Page 9: ... service valve and the hole in the vapor disc 5 After the disc has been removed burnish the external sur faces and clean the internal surfaces of the vapor connec tion and the vapor piping The vapor line can now be brazed to the vapor connection on the outdoor unit while maintaining the flow of dry nitrogen Aftertheliquidandvaporlineshavebeeninstalled thesystem should be evacuated and charged EVAC...

Page 10: ...1 The outdoor design temperature 2 The building heat loss at the outdoor design temperature and 3 The heating capacity of the system at the outdoor design temperature Refer to Form 515 41 AD1 to determine balance point Referto 035 05163 001 for details regardingthe outdooram bient balance point control accessory Model No 2BP11700224 10 Unitary Products Group 035 15410 002 B 0404 FIG 6 EXTENDING TH...

Page 11: ...Unitary Products Group 11 035 15410 002 B 0404 FIG 7 REFRIGERANT FLOW DIAGRAM ...

Page 12: ...035 15410 002 B 0404 12 Unitary Products Group FIG 8 CHARGING CURVE EFB090 FIG 9 CHARGING CURVE EFB120 ...

Page 13: ... temperature reaches 255 F 2TH thermostat will open and the defrost control board will lock out the compressor If the suction pressure falls to 7 psig the low pressure switch will open and the defrost control will lock out the compressor 8 If the control that caused the lockout has automatically re set the unit can be restarted by one of the following a Turning the system switch on the thermostat ...

Page 14: ... defrost cycle will be terminated when a the liquid temperature exceeds 55 F or b 10 minutes have passed since defrost initiation The 10 minute cycle time independent of liquid line tem perature is controlled by the defrost control board 4 At defrost termination the unit returns to the normal heat ing operation OPERATION BELOW 0 F OUTDOOR TEMPERATURE 1 At 0 F outdoor temperature the low temperatur...

Page 15: ...or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been operating for several minutes shut off the main power supply at the disconnect switch and in spect all factory wiring connections and bolted surfaces for tightness SAFETY FEATURES 1 All outdoor fan motors have inherent protection with auto...

Page 16: ...s Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright 2004 by York International Corporation All Rights Reserved 035 15410 002 B 0404 Supersedes 035 15410 002 A 0304 ...

Reviews: