background image

Before starting the installation, select and check the suitability
of the location for both the indoor and outdoor unit. Observe all
limitations and clearance requirements, see Figure 2.

The outdoor unit must have sufficient clearance for air entrance
to the condenser coil, for air discharge and for service access.

If the unit is to be installed on a hot sun exposed roof or a
black-topped ground area, the unit should be raised sufficiently
above the roof or ground to avoid taking the accumulated layer
of hot air into the outdoor unit.

Provide an adequate structural support.

The unit may be installed at ground level on a solid base that
will not shift or settle, causing strain on the refrigerant lines and
possible leaks. Maintain the clearances shown Figure 2 and
install the unit in a level position. Isolate the base from the
building structure to avoid noise or vibration transmission.

When installing units on a roof, the structure must be capable
of supporting the total weight of the unit, including a pad, lintels,
rails, etc., which should be used to minimize the transmission
of sound or vibration into the conditioned space.

Isolate the unit from rain gutters to avoid any possible wash out
of the foundation.

Normal operating sound levels may be objectionable if the unit
is placed directly under windows of certain rooms (bedrooms,
study, etc.).

Condensate will drain from beneath the coil of the outdoor unit
during the defrost cycle. Normally this condensate may be
allowed to drain directly onto the ground. A gravel bed may be
used to prevent mud splashing.

WARNING: The outdoor unit should not be installed in an area

where mud or ice could cause personal injury.
Remember that condensate will drip from the unit
coils during heat and defrost cycles and that this
condensate will freeze when the temperature of the
outdoor air is below 32

°

F.

Elevate the unit sufficiently to prevent any blockage of the air
entrances by snow in areas where there will be snow accumu-
lation. Check the local weather bureau for the expected snow
accumulation in your area.

INSTALLATION PROCEDURES

The following sequence of installation steps is suggested.

1. Inspect unit and set in place.

2. Make electrical power connections.

3. Check orifice size and replace with correct size if neces-

sary. 

UNIT MODEL  E1FB / E9FB...

012

018

024

030

UNIT SUPPLY VOLTAGE

208/230-1-60

NORMAL VOLTAGE RANGE

1

187 to 252

MIN. CIRCUIT AMPACITY

12.0

12.0

15.2

19.2

MAX. OVERCURRENT DEVICE AMPS

2

15

15

20

25

COMPRESSOR AMPS

RATED LOAD

7.4

7.4

9.7

12.3

LOCKED ROTOR

48

48

60

73

CRANKCASE HEATER

YES

YES

YES

YES

FAN MOTOR AMPS

RATED LOAD

0.8

0.8

0.8

0.8

LOCKED ROTOR

1.9

1.9

1.9

1.9

MIN. FIELD WIRE SIZE AWG.
COPPER CONDUCTORS

60°C

14

14

12

12

MAX. WIRE LENGTH ( FEET)
BASED ON 3% VOLTAGE DROP

208V

77

77

99

81

230V

86

86

110

90

FAN DIAMETER INCHES

18

18

18

18

FAN MOTOR

RATED HP

1/8

1/8

1/8

1/4

NOMINAL RPM

1075

1075

1075

1075

NOMINAL CFM

2000

2000

1900

2200

COIL

FACE AREA SQ. FT.

15.1

15.1

14.1

14.1

ROWS DEEP

1

1

2

2

FINS/INCH

16

16

13

13

LIQUID LINE CONNECTION

5/16

5/16

5/16

5/16

VAPOR LINE CONNECTION

5/8

5/8

5/8

3/4

OPERATING WEIGHT LBS.

148

148

170

172

(1) Utilization range “A” in accordance with ARI standard 110.
(2) Dual element fuses or HACR circuit breaker.

TABLE 2 - PHYSICAL AND ELECTRICAL DATA

515.26-N1Y

2

Central Environmental Systems

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: