background image

tion. However, if another orifice should be used, see the coil
instruction for details to change the orifice in the coil.

QUICK CONNECT SYSTEMS

Indoor coils and outdoor units are to be connected with pre-
charged interconnecting tubing specified for the split systems.
The units and the lines are equipped with sealed one-time
quick-connect couplings which, when screwed together, will
have their seals broken, allowing for free passage of refriger-
ant. One end of the tubing contains a female fitting for connect-
ing to the outdoor unit. The other end has a male fitting with a
90

°

 bend on the vapor line for connecting to the indoor coil.

The outdoor end of the lines have capped service (Schrader)
ports. Install the coupling in a position that will permit a
Schrader tool to be attached to the service port.

Prepare and connect fittings as follows:

1. Begin at either the indoor coil or the outdoor unit. Remove

only one dust cap at a time to avoid damage and to prevent
dirt from getting into the other. If necessary, carefully wipe
seals and threaded surfaces with a clean cloth.

2. Lubricate the male half diaphragm and the “O” ring with

several drops of refrigerant oil. Thread the halves together
by hand to insure proper mating of the threads. Use proper
size wrenches (on both the body hex and on the union nut)
and tighten until bodies “bottom” or a definite resistance is
felt.

3. Using a marker or ink pen, mark a line lengthwise from the

union nut to the unit panel. Then tighten an additional 1/4
turn (90

°

 from the mark on the panel to the mark on the

union nut).

4. Repeat this procedure with the other three in the system,

removing the dust cap just prior to making the connection.

5. Leak test all refrigerant piping connections including the

service port flare caps to be sure they are leak tight.

DO NOT OVERTIGHTEN (between 40 and 60 inch-lbs.
maximum).

6. Do not remove the flare caps from the service ports except

when necessary for servicing the system.

CAUTION: Do not connect manifold gauges unless trouble is

suspected. Approximately 3/4 ounce of refrigerant
will be lost each time a standard manifold gauge is
connected.

7. The quick connect outdoor unit contains enough refrigerant

charge for a matched evaporator. Refer to Table 3 for the
amount of additional charge required for some mix-
matched indoor coils. If additional charge is required, see
recommended charging methods.

SWEAT-CONNECT SYSTEMS

The outdoor units have re-usable service valves on both the
liquid and vapor connections.  The total system refrigerant
charge is retained within the outdoor unit during shipping and
installation. The re-usable service valves are provided to
evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate
precautions to assure an internally clean and dry system.

Always use refrigeration-grade copper tubing that is internally
clean and dry for refrigerant lines. Use clean hard drawn copper
tubing where no appreciable amount of bending around ob-
struction is necessary. If soft copper must be used, care must
be taken to avoid sharp bends which may cause a restriction.
The vapor line must be insulated with a minimum of 1/2 inch
insulation (Arm-A-Flex or equivalent).

CAUTION: Dry nitrogen should always be supplied through

the tubing while it is being brazed, because the
temperature required is high enough to cause oxi-
dation of the copper unless an inert atmosphere is
provided. The flow of dry nitrogen should continue
until the joint has cooled. Always use a pressure
regulator and safety valve to insure that only low
pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and
prevent oxidation.

All outdoor unit and evaporator coil connections are copper-to-
copper and should be brazed with a phosphorous-copper alloy
material such as Silfos-5 or equivalent. DO NOT use soft
solder.

BASE VALVE CONNECTION PRECAUTIONS

Precautions should be taken to prevent heat damage to the
fitting by wrapping a wet rag around it as shown in Figure 7.
Also, protect all painted surfaces and insulation during brazing.
After brazing - cool joint with wet rag.

WARNING: This is not a backseating valve. The service access

port has a valve core. Opening or closing valve
does not close service access port.

LABEL

LEFT-HAND THREAD

DISTRIBUTOR

ORIFICE

LIQUID LINE
FITTING

WITH  #65

ORIFICE

COIL EQUIPPED

FIGURE 6 - ORIFICE LABEL

515.26-N1Y

Central Environmental Systems

7

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: