background image

EVACUATION

It will be necessary to evacuate the system if the unit has
developed a leak during shipment or was, for any other reason,
opened to the atmosphere. If a leak is suspected, leak test to
locate the leak. Repair the leak and test again.

WARNING: Never attempt to repair any brazed connections

while the system is under pressure. Personal injury
could result.

To verify if the system has no leaks, simply close the valve to
the vacuum pump suction to isolate the pump and hold the
system under vacuum. Watch the micron guage for a few
minutes. If the micron gauge indicates a steady and continuous
rise, it’s an indication of a leak. If the gauge shows a rise, then
levels off after a few minutes and remains fairly constant, its an
indication that the system is leak free but still contains moisture
and may require further evacation if the reading is above 500
microns.

SYSTEM CHARGE

The factory charge in the outdoor unit is listed in Table 3 and
includes enough charge for the unit and matched indoor coils.
Sweat connect units also include sufficient charge for 15 feet
of lines. Pre-charged line lengths are factory charged with the
correct amount of refrigerant required.

Sweat connect installations over 15 feet long and some indoor
coil matches may require some additional charge. Table 4 lists
the amount of any additional refrigerant required for line lengths
over 15 feet.

The “TOTAL SYSTEM CHARGE” must be permanently
stamped on the unit data plate.

Total system charge is determined as follows:

1. Determine the outdoor unit charge from Table 3.

2. Determine indoor coil adjustment from Table 3.

3. Calculate the line charge with the factors in Table 4.

a) Calculate total length of pre-charged lines for quick

connect units.

b) Calculate over 15 feet of sweat lines for sweat connect

units.

NOTE: The charge for pre-charged lines should be included

in the system charge shown on the data plate but need
not be added to the system. If sweat connect lines are
used, the line charge over 15 feet should be included
on the data plate and must be added to the system.

4. Total system charge = item 1 + item 2 + item 3.

5. Permanently stamp the unit data plate with the total amount

of refrigerant in the system.

Use the following charging method whenever additional refrig-
erant is required for the system charge.

CAUTION: Refrigerant charging should only be carried out by

a qualified air conditioning contractor.

Measurement Method

A calibrated charging cylinder or accurate weighing device
must be used to add  refrigerant.

Check flare caps on service ports to be sure they are leak tight.
DO NOT OVERTIGHTEN (between 40 and 60 inch-lbs. maxi-
mum).

OWNER’S INSTRUCTION

Assist owner with processing warranty cards. Review User’s
Information Manual and provide a copy for the owner guidance
on proper operation and maintenance. Instruct the owner or the
operator how to start, stop and adjust temperature setting. The
owner should also be instructed about the 5 minute off cycle
timer and the defrost operation.

When applicable, instruct the owner that the compressor is
equipped with a crankcase heater to prevent the migration of
refrigerant to the compressor during the “OFF” cycle. The
heater is energized only when the unit is not running. If the main
switch is disconnected for long periods of shut down, do not
attempt to start the unit for 8 hours after the switch has been
connected. This will allow sufficient time for all liquid refrigerant
to be driven out of the compressor.

The installer should also instruct the owner on proper operation
and maintenance of all other system components.

LIQUID OD

VAPOR OD

R-22 CHARGE

OZ./FT.

5

16

5

8

0.44

5

16

3

4

0.46

5

16

7

8

0.48

TABLE 4 - REFRIGERANT LINE CHARGES

515.26-N1Y

Central Environmental Systems

9

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: