background image

WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER’S APPROVAL.

INDICATIONS OF PROPER OPERATION

COOLING 

Cooling operation is the same as any conventional air condi-
tioning unit.

1. The outdoor fan should be running, with warm air being

discharged from the top of the unit.

2. The indoor blower (furnace or air handler) will be operating,

discharging cool air from the ducts.

3. The vapor line at the outdoor unit will feel cool to the touch.

4. The liquid line at the outdoor unit will feel warm to the touch.

HEATING

Indications of proper Heating operation is as follows:

1. The outdoor fan should be running, with cool air being

discharged from the top of the unit.

2. The indoor blower (furnace or air handler) will be operating,

discharging warm air from the ducts.

3. The vapor line at the outdoor unit will feel warm to the touch.

4. The liquid line at the outdoor unit will feel cool to the touch.

SYSTEM OPERATION

See Figure 9  to trace the flow of refrigerant through the system.

WITH POWER TO UNIT AND THERMOSTAT IN COOLING
POSITION.

1. Reversing valve is energized through thermostat system

switch to position refrigerant circuit for cooling operation. In
the cooling cycle, discharge gas is pumped to the outdoor
coil which is the condenser. The indoor coil is the evapora-
tor.

2. If fan switch is in “ON” position, a circuit is made through

blower relay to provide continuous blower operation.

3. When thermostat cooling contact closes, a circuit is made

to energize contactor and start the system, if the compres-
sor has been off 5 minutes. With fan switch in “AUTO”
position, a circuit is made from thermostat cooling contact
through blower relay to provide blower operation.

4. System will cycle with thermostat demand to provide cool-

ing as needed.

WITH POWER TO UNIT AND THERMOSTAT IN HEATING
POSITION

1. Reversing valve is de-energized to position refrigerant

circuit for heating operation. In the heating cycle, discharge
gas is pumped to the indoor coil which is the condenser.
The outdoor coil is the evaporator.

2. If fan switch is in “ON” position, a circuit is made through

blower relay to provide continuous blower operation.

3. When first stage of thermostat heating contact closes, a

circuit is made through the control to energize contactor

FLOW
CONTROL
DEVICE

INDOOR
COIL

STRAINER

COMPRESSOR

4-WAY
REVERSING
VALVE*

SUCTION
ACCUM.

CAPILLARY TUBE
EXPANSION DEVICE

OUTDOOR
COIL

COOLING CYCLE FLOW

HEATING CYCLE FLOW

* SHOWN IN COOLING POSITION

FILTER/ DRIER-CHECK VALVE

FIELD CONNECTED LINE

FIELD CONNECTED LINE

FIGURE 9 - HEAT PUMP FLOW DIAGRAM

515.26-N1Y

10

Central Environmental Systems

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: