background image

4. Route the vapor and liquid lines.

5. Connect tubing and leak test.

6. Make electrical control connections.

7. Charge system.

8. Instruct owner.

UNIT PLACEMENT

1. Provide a base in the pre-determined location.

2. Remove the shipping carton and inspect for possible dam-

age.

3. Compressor tie-down bolts should remain tightened.

4. Position the unit on the base provided.

5. Sit unit on the (4) rubber elevating grommets provided with

the unit. These should be positioned as shown in Figure 1
to reduce noise and allow for proper drainage.

6. Make a hole(s) in the structure wall large enough to accom-

modate the insulated vapor line, the liquid line and the
wiring.

ELECTRICAL CONNECTIONS

1. Check the electrical supply to be sure that it meets the

values specified on the unit nameplate and wiring label.

2. Remove proper low voltage knockout. Remove plastic snap

bushing from instruction packet and insert in low voltage
knockout hole.

3. The complete connection diagram and schematic wiring

label is located on the inside surface of the unit electrical
box cover. Typical Field Wiring is shown in Figure 3.

4. All field wiring to be in accordance with national electrical

code (NEC) and/or local city codes.

NOTE: Power wiring, disconnect switch, and overcurrent pro-

tection to be supplied by installer. See Physical and
Electrical Data Table for proper sizes. USE COPPER
CONDUCTORS ONLY. Unit must be grounded with a
separate ground conductor wire.

5. Install the proper size weatherproof disconnect switch out-

doors and within sight of the unit.

6. Run power wiring from the disconnect switch to the unit.

7. Install the proper size time-delay fuses or circuit breaker,

and make the power supply connections.

8. Energize the crankcase heater, if applicable, to save time

by preheating the compressor oil while the remaining instal-
lation is completed.

RUBBER
ELEVATING
GROMMETS
(4)

Note: Do Not  block drainage
           holes with grommets.

UNIT
BASE
PAN

FIGURE 1 - POSITIONING OF RUBBER ELEVATING
GROMMETS

12" REAR
AND SIDES

TO POWER
SUPPLY

48" OVERHEAD
CLEARANCE

24" SERVICE
ACCESS

WEATHERPROOF
DISCONNECT
SWITCH

NEC CLASS 1
WIRING

TO
BLOWER
MOTOR
RELAY

NEC CLASS 2
WIRING

TO
INDOOR
COIL

SEAL OPENING(S)  WITH 
PERMAGUM OR EQUIVALENT

THERMOSTAT

NOTE:  ALL OUTDOOR WIRING
             MUST BE WEATHERPROOF

Sit unit on
rubber
elevator
grommets to
reduce noise
and allow for
proper
drainage.

Check local weather bureau for snow
accumulation / clearance

FIGURE 2 - TYPICAL INSTALLATION

515.26-N1Y

Central Environmental Systems

3

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: