background image

DEFROST 

The unit has a demand defrost control.

During troubleshooting, defrost can be initiated by shorting
defrost test pins on the module. The pins are about 1/2" long
and mounted on the upper right hand side of the defrost
control.

TUBING CONNECTIONS

Sweat-connect systems must use field supplied, clean, dehy-
drated refrigeration-grade copper tubing.

Quick-connect systems must use pre-charged refrigerant line
sets (quick-connect couplings) designated for the respective
unit size and available from CES. Pre-charged lines with ex-
cess tubing should be coiled horizontally in an inconspicuous
location to avoid oil trapping.

Stub kits are available to field fabricate quick connect line sets
or to connect mix-matched units and coils.

Unit should be installed only with  approved system combina-
tions (indoor coil/outdoor unit) specified in Technical Guide.

See Application Data,"General Piping Recommendations and
Refrigerant Line Length," for vapor and liquid line sizing, cal-
culation of liquid line pressure loss or gain, determination of
vapor line velocity, elevation limitations, orifice corrections,
system charging, traps, etc.

Total line lengths are limited to 75 feet due to the storage
capacity of the accumulator. Systems with total line lengths
over 50 feet must be provided with a low voltage start kit.

Elevation differences are limited to:

Indoor Above Outdoor ....... 50 ft.
Outdoor Above Indoor ....... 50 ft.

Systems with liquid line pressure loss or gain greater than 11
psi must be provided with corrected orifice size.

Inter-connecting refrigerant lines should be sized to match the
factory supplied fittings. Liquid lines must NEVER be increased
or decreased. Vapor lines may be increased one size to mini-
mize pressure drop as long as a velocity of at least 1000 feet
per minute is maintained.

Additional charge is required for inter-connecting piping greater
than 15 feet for sweat units and some indoor coil matches.

The lines should be installed so that they will not obstruct
service access to the coil, air handling system or filter. Install
the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Care must also
be used to isolate the refrigerant lines to minimize noise
transmission from the equipment to the structure.

Tape and suspend the refrigerant lines as shown. DO NOT
allow metal-to-metal contact.

Use PVC piping as a conduit for all underground installations
as shown below. Buried lines should be kept as short as
possible to minimize the build up of liquid refrigerant in the
vapor line during long periods of shutdown.

LIQUID

LINE

TAPE

SHEET
METAL
HANGER

INSULATED
VAPOR LINE

FIGURE 4 - TUBING HANGER

TO INDOOR COIL

TO OUTDOOR UNIT

LIQUID LINE

CAP

PVC

CONDUIT

INSULATED

VAPOR LINE

FIGURE 5 - UNDERGROUND INSTALLATION

515.26-N1Y

Central Environmental Systems

5

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: