background image

and start the system, if the compressor has been off 5
minutes. With fan switch in “AUTO” position, a circuit is
made from thermostat heating contact through blower relay
to provide blower operation.

4. The system will cycle in response to thermostat signal to

provide heating as needed.

5. Supplemental electric heaters are energized by second

stage of heating thermostat.

TEST PINS

The test pins labeled “speed-up” and “defrost” are provided to
aid in field servicing of the E*FB heat pump. See Figure 10.
The pins are designed to be temporarily shorted together either
by a screwdriver or with a 1/4" female spade connector.

When the “speed-up” pins are shorted together, ALL timings
are speeded up by a factor of 64. This reduces the anti-recycle
compressor timer from 5 minutes to about 5 seconds and the
defrost terminate time from 14 minutes to 13 seconds: addi-
tionally, the 39 minute minimum run time would be shorteded
to about 40 seconds or less if the system has operated for some
period of time since last defrost.

When the “defrost” pins are shorted together, the control will
allow the unit to go into a defrost cycle if the compressor is
operating. When the short is removed, the heat pump will
remain in defrost until the coil temperature reaches 75

°

 or 14

minutes expires.

If the liquid (coil) temperature happens to be above 75

°

F, the

short must be maintained to keep the unit in a defrost cycle. It
should be noted that caution should be used since the unit WILL
REMAIN in defrost unitl the short is removed regardless of coil

temperature. This could cause a lockout due to high discharge
pressure!

NOTE:  Anytime the “defrost” shorting pins are jumpered, it

automatically resets all timing cycles. After a power
failure, all timing cycles would also reset except one
that is the 5 minute delay for compressor restart. It can
be reduced, however, by jumpering the “speed-up”
pins on the control board.

DEFROST CYCLE

Frost and ice which forms on the outdoor coil during the heating
cycle must be defrosted when it blocks the air flow through the
coil.

Due to the arrangement of the refrigerant circuit within the
outdoor coil of these units, frost may accumulate unevenly in
different sections of the coil. However, a normal defrost may
occur even though the coil is not completely covered with frost.

Three requirements must be met before a defrost cycle can be
initiated.

1. A minimum of 39 minutes must have elapsed since last

defrost.

2. The liquid line temperature must be less than 40

°

F.

3. The coil temperature must be below the defrost initiation

temperature for 4.5 minutes continuously.

NOTE:  Under certain low ambient conditions normal trigger-

ing of a defrost cycle could be prevented. Therefore as
a precautionary measure a “Forced Defrost” is initiated
every six hours to insure compressor longevity by return-
ing oil back to the sump.

Defrost will terminate when the coil temperature reaches 75

°

F

or after 14 minutes defrost time.

LOCK-OUT CONTROL

If the discharge pressure reaches 400 PSIG, during either the
heating or cooling mode, a lock-out will occur. A lock-out will
turn on the emergency heat light on the thermostat. 

Turning the thermostat switch to “off” then back to “on” will reset
the system.

OPERATION IN EMERGENCY HEAT POSITION

When switch on thermostat is placed in emergency heat posi-
tion:

1. Emergency light is energized.

2. Compressor circuit is locked out.

3. Supplemental and standby heaters (if installed) will be

controlled by first stage of heating thermostat.

FIGURE 10- DEFROST TEST PINS

SPEED-UP
TEST PINS

DEFROST
TEST
PINS

515.26-N1Y

Central Environmental Systems

11

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: