background image

Pack fiber glass insulation and a sealing material such as
permagum around refrigerant lines where they penetrate a wall
to reduce vibration and to retain some flexibility.

Do not install a filter drier since one is factory installed in every
outdoor unit.

Insulate all vapor lines with a minimum of 1/2" foam rubber.
Liquid lines that will be exposed to direct sunlight and/or high
temperatures must also be insulated.

ORIFICE SELECTION

YORKMATE FLOW CONTROL COILS

NOTE: The proper orifice must be installed in the evaporator

coil liquid connection prior to the connection of the
refrigerant lines.

WARNING: Coil (whether sweat or quick connect) is under 15

PSIG pressure.

Each coil will have an orifice installed in the fitting between the
liquid line connection and distributor. The orifice is identified on
a label next to the liquid connection as shown in Figure 6.

The orifice that is shipped with the coil is based on the “most
sold” combination, but it may have to be changed, depending
on the capacity and efficiency of the outdoor unit, elevation
differences, and/or long total line lengths. An additional ori-
fice(s) is shipped with most outdoor units in the literature packet
for the most commonly required replacement combinations.
Other sizes must be ordered from the Parts Department if
required.

Table 3 shows the orifice and charge adjustment for approved
system combinations (indoor coil/outdoor unit).  See Applica-
tion Data,"General Piping Recommendations and Refrigerant
Line Lengths" for long line lengths and elevation differences.

If the orifice sizes match, nothing further is required and the
refrigerant lines may be connected per the outdoor unit instruc-

OUTDOOR UNIT   E1FB / E9FB...

012

018

024

030

UNIT ORIFICE(S)

1

55

55

61, 63

67, 69

FACTORY   R-22
CHARGE, LBS. OZ.

SWEAT

5-0

5-5

7-10

7-10

QUICK

4-9

4-14

7-3

7-3

INDOOR COIL

COIL

ORIFICE2

SYSTEM O ADDITIONAL CHARGE, OZ.

G3HC / G1FC018

55

55+9

55+0

-

-

G3HC / G1FC024

61

-

55+9

61+3

-

G3HC / G1FC030

69

-

-

63+13

69+15

G3HC / G1FC036

81

-

-

-

69+23

G3HC / G1FC042

78

-

-

-

-

G3HC / G1FC048

90

-

-

-

-

G3HC / G1FC060

96

-

-

-

-

G3US018

55

55+9

55+5

-

-

G3UA024

59

-

55+9

61+3

-

G3UA030

65

-

-

63+1

-

G3UA036

69

-

-

63+12

69+13

G3UA037

69

-

-

63+12

69+13

G3UA048

87

-

-

-

-

G3UA060

96

-

-

-

-

G3UA061

96

-

-

-

-

G2UT024

-

-

-

+3

-

G2UT036

-

-

-

-

+13

G2UT037

-

-

-

-

+13

G3CN030

65

55+28

55+23

63+11

67+20

G3CN042

73

-

-

-

-

G3CN060

87

-

-

-

-

F1SA / F1SF018

53

55+0

53+2

-

-

F1SA / F1SF024

61

-

55+3

61+0

-

F1SA / F1SF030

67

-

-

61+0

67+10

F1SA / F1SF036

81

-

-

-

67+14

1These orfices are packed in the instruction/warranty packet of each outdoor unit.

2

These orifices are factory-mounted in the flow control device of each indoor coil.

NOTE:  Orifices in (   ) must be ordered from the Parts Department.

TABLE 3- ADDITIONAL R-22 CHARGE/ORIFICE SIZE

515.26-N1Y

6

Central Environmental Systems

Summary of Contents for E1FB012

Page 1: ...WARNING NOTES are intended to clarify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment dam...

Page 2: ...ent mud splashing WARNING The outdoor unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the unit coils during heat and defros...

Page 3: ...ith national electrical code NEC and or local city codes NOTE Power wiring disconnect switch and overcurrent pro tection to be supplied by installer See Physical and Electrical Data Table for proper s...

Page 4: ...or X W Y 7 WIRES OUTDOOR UNIT THERMOSTAT INDOOR UNIT T2 POWER WIRING 208 230 1 60 POWER WIRING 24V CONTROL WIRING NEC CLASS 2 CIRCUIT THERMOSTAT Jumper terminals E and W to heat on first stage during...

Page 5: ...evation differences are limited to Indoor Above Outdoor 50 ft Outdoor Above Indoor 50 ft Systems with liquid line pressure loss or gain greater than 11 psi must be provided with corrected orifice size...

Page 6: ...er sizes must be ordered from the Parts Department if required Table 3 shows the orifice and charge adjustment for approved system combinations indoor coil outdoor unit See Applica tion Data General P...

Page 7: ...ected 7 The quick connect outdoor unit contains enough refrigerant charge for a matched evaporator Refer to Table 3 for the amount of additional charge required for some mix matched indoor coils If ad...

Page 8: ...se the system refrigerant in the outdoor unit to purge or leak test 8 Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVERTIGHT...

Page 9: ...s for sweat connect units NOTE The charge for pre charged lines should be included in the system charge shown on the data plate but need not be added to the system If sweat connect lines are used the...

Page 10: ...e discharge gas is pumped to the outdoor coil which is the condenser The indoor coil is the evapora tor 2 If fan switch is in ON position a circuit is made through blower relay to provide continuous b...

Page 11: ...les After a power failure all timing cycles would also reset except one that is the 5 minute delay for compressor restart It can be reduced however by jumpering the speed up pins on the control board...

Page 12: ...ilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur...

Reviews: