10-23
IM 05P01C31-01EN
Output
(Control
and
Retransmission)
Functions
10
10.12 Setting Preset Output Value
10.12.3
Setting Output Value When Error Occurs (Input Error Preset Output)
Description
The 0% control output, 100% control output, or input preset output can be selected and
output as input error preset output in the following conditions.
• The input burnout occurs during operation in AUTO or CAS mode and RUN mode.
• The ADC error occurs during operation in AUTO or CAS mode and RUN mode.
However, the manual output becomes the output when the input burnout occurs in MAN
mode and RUN mode.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
EPO
Input error preset
output
STD
0: Preset output
1: 0% output
2: 100% output
SYS
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...