When the Heating Side is in ON/OFF Control and the Cooling Side is in PID Control:
The following shows the formula and operation example.
HOUT = OUT > ( 50% + + )
Other than this case, maintain current state.
Output turns on when
2
DB
2
HYS
*: OUT: control output, HOUT: heating-side control output,
COUT: cooling-side control output, DB: dead band, and
HYS: heating-side hysteresis
COUT = ( 50%
–
OUT
–
) × 2
2
DB
Positive Dead Band
0%
Dead band
(DB)
Dead
band
(DB)
Hysteresis (HYS)
Cooling-side control output (%)
Heating-side control output (%)
0%
50%
Control computation output
100%
100%
Cooling-side
control output
high limit
(OHc)
0%
100%
0%
50%
100%
(OUT)
Negative Dead Band
0%
0%
50%
100%
100%
0%
100%
0%
50%
100%
Dead band
(DB)
Dead band
(DB)
Hysteresis (HYS)
Cooling-side control output (%)
Heating-side control output (%)
Control computation output
Cooling-side
control output
high limit
(OHc)
(OUT)
8.2 Setting Control Type (CNT)
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...