18-9
IM 05P01C31-01EN
Parameters
18
SELECT Parameter Menu (Menu: CS)
Parameter
symbol
Name
Display
level
Setting range
Initial value
CS10 to
CS19
SELECT parameter
10 to 19
EASY
Setting range of a registered
parameter.
-
SP and Alarm Setpoint Setting Menu (Menu: SP)
Parameter
symbol
Name
Display
level
Setting range
Initial value
SP
Target setpoint
EASY
0.0 to 100.0% of PV input range
(EU) (Setting range: SPL to SPH) SPL
SUB
Sub-target setpoint
(in Two-position
two-level control)
EASY
Set the offset from SP.
-100.0 to 100.0% of PV input range
span (EUS)
0.0 % of PV
input range
span
PIDN
PID number
selection
EASY
1 to 8 (Depends on the PIDG.
setting.)
Same as SP
number.
A1 to A8
Alarm-1 to -8
setpoint
EASY
Set a display value of setpoint of
PV alarm, SP alarm, deviation
alarm, output alarm, or velocity
alarm.
-19999 to 30000 (Set a value
within the input range.)
Decimal point position depends on
the input type.
0
In Cascade control, the following parameters are also displayed for secondary loop. (the LP2 lamp
is lit)
• Parameter: SP, SUB, PIDN, A1 to A8
SP-related Setting Menu (Menu: SPS)
Parameter
symbol
Name
Display
level
Setting range
Initial value
RMS
Remote input
method
STD
RSP: Via remote (aux. analog)
input
COM: Via communication
RSP
RFL
Remote input filter
STD
OFF, 1 to 120 s
OFF
RT
Remote input ratio
STD
0.001 to 9.999
1.000
RBS
Remote input bias
STD
-100.0 to 100.0% of PV input range
span (EUS)
0.0 % of PV
input range
span
UPR
SP ramp-up rate
EASY
OFF, 0.0 + 1 digit to 100.0% of PV
input range span (EUS)
OFF
DNR
SP ramp-down rate
EASY
OFF
TMU
SP ramp-rate time
unit
EASY
HOUR: Ramp-up rate or ramp-
down rate per hour
MIN: Ramp-up rate or ramp-down
rate per minute
HOUR
SPT
SP tracking
selection
STD
OFF, ON
ON
PVT
PV tracking
selection
STD
OFF, ON
OFF
In Cascade control, the following parameters are also displayed for secondary loop. (the LP2 lamp
is lit)
• Parameter: RMS, RFL, RT, RBS, UPR, DNR, TMU, SPT, PVT
18.2 List of Parameters
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...