19-2
IM 05P01C31-01EN
19.1.1 Input Specifications
Universal Input
• Number of inputs: 1
• Input type, instrument range, and measurement accuracy: See the table below.
Input Type
Instrument Range (
°
C)
Instrument Range (
°
F)
Accuracy
Thermo-
couple
K
-270.0
to
1370.0°C
-450.0
to 2500.0
°
F
±0.1% of instrument range ±1 digit for 0°C or more
±0.2% of instrument range ±1 digit for less than 0°C
±2% of instrument range ±1 digit for less than
-200.0°C of thermocouple K
±1% of instrument range ±1 digit for less than
-200.0°C of thermocouple T
-270.0
to
1000.0°C
-450.0
to
2300.0°F
-270.0
to
500.0°C
-200.0
to
1000.0°F
J
-200.0
to
1200.0°C
-300.0
to
2300.0°F
T
-270.0
to
400.0°C
-450.0
to
750.0°F
0.0
to
400.0°C
-200.0
to
750.0°F
B
0.0
to
1800.0°C
32
to
3300°F
±0.15% of instrument range ±1 digit for 400°C or
more
±5% of instrument range ±1 digit for less than
400°C
S
0.0
to
1700.0°C
32
to
3100°F
±0.15% of instrument range ±1 digit
R
0.0
to
1700.0°C
32
to
3100°F
N
-200.0
to
1300.0°C
-300.0
to
2400.0°F ±0.1% of instrument range ±1 digit
±0.25% of instrument range ±1 digit for less than 0°C
E
-270.0
to
1000.0°C
-450.0
to
1800.0°F
±0.1% of instrument range ±1 digit for 0°C or more
±0.2% of instrument range ±1 digit for less than 0°C
±1.5% of instrument range ±1 digit for less than
-200.0°C of thermocouple E.
L
-200.0
to
900.0°C
-300.0
to
1600.0°F
U
-200.0
to
400.0°C
-300.0
to
750.0°F
0.0
to
400.0°C
-200.0
to
1000.0°F
W
0.0
to
2300.0°C
32
to
4200°F ±0.2% of instrument range ±1 digit (Note 2)
Platinel 2
0.0
to
1390.0°C
32.0
to
2500.0°F ±0.1% of instrument range ±1 digit
PR20-40
0.0
to
1900.0°C
32
to
3400°F
±0.5% of instrument range ±1 digit for 800°C or
more
Accuracy is not guaranteed for less than 800°C.
W97Re3-
W75Re25
0.0
to
2000.0°C
32
to
3600°F ±0.2% of instrument range ±1 digit
RTD
JPt100
-200.0
to
500.0°C
-300.0
to
1000.0°F ±0.1% of instrument range ±1 digit (Note 1)
-150.00 to
150.00°C
-200.0
to
300.0°F ±0.1% of instrument range ±1 digit
Pt100
-200.0
to
850.0°C
-300.0
to
1560.0°F
±0.1% of instrument range ±1 digit (Note 1)
-200.0
to
500.0°C
-300.0
to
1000.0°F
-150.00 to
150.00°C
-200.0
to
300.0°F ±0.1% of instrument range ±1 digit
Standard signal
0.400 to
2.000 V
±0.1% of instrument range ±1 digit
1.000 to
5.000 V
4.00 to 20.00 mA
DC voltage/current
0.000 to
2.000 V
0.00 to
10.00 V
0.00 to 20.00 mA
-10.00 to
20.00 mV
0.0 to
100.0 mV
The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power
frequency at 50/60 Hz.
Note 1: ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range between
-100 and 200°C.
Note 2: W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988
19.1 Hardware Specifications
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...