8-97
IM 05P01C31-01EN
Control Functions
8.4.6 Setting Hysteresis at Time of PID Switch
Description
When the zone PID selection is selected, hysteresis at time of each zone switch can be
set.
The following shows the operation example of hysteresis at time of zone switch.
Reference point 1
PV
Hysteresis
0.5% of PV input range span
PID of group 1
PID of group 2
PID of group 1
PID of group 2
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
RHY
Zone PID switching
hysteresis
STD
0.0 to 10.0% of PV input
range span (EUS)
ZONE
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
8.4.7 Switching PID by Contact Input
Description
PID can be switching by contact input.
Setting Details
►
Contact input assignment: 12.1 Setting Contact Input Function
8
8.4 Switching PID
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...