9-5
IM 05P01C31-01EN
Auxiliary Control Functions
9
9.4 Forcing SP to Track Remote Input (SP Tracking)
Description
SP tracking function is the function to force the local setpoint (SP) to track the remote
setpoint (RSP) when the operation mode is switched from REM (remote) to LCL (local)
mode.
The function is effective to prevent abrupt PV changes.
REM → LCL mode switch
Time
REM → LCL mode switch
Time
SP tracking enabled
SP tracking disabled
PV
PV
SP
RSP
SP
RSP
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SPT
SP tracking selection
STD
OFF, ON
SPS
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...