9-3
IM 05P01C31-01EN
Auxiliary Control Functions
9
70
ºC
/min
UPR = 140/2 = 70 (
ºC
/min)
Temperature rise time of 2 min.
SP of group 2
SP of group 1
SP of group 2= 640
ºC
SP of group 1 = 500
ºC
SP switch
Temperature
difference of 140
ºC
UPR =
=
Time (min)
Temperature difference (ºC)
= 70 (ºC/min)
2 min
140ºC
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
UPR
SP ramp-up rate
EASY
OFF, 0.0 + 1 digit to 100.0% of PV
input range span (EUS)
SPS
DNR
SP ramp-down rate
EASY
TMU
SP ramp-rate time
unit
EASY
HOUR: Ramp-up rate or ramp-
down rate per hour
MIN: Ramp-up rate or ramp-down
rate per minute
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
9.2 Changing SP at a Fixed Rate (SP Ramp-Rate Setting Function)
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...