Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 28
no. Param.
Description
Dec.
Point
Values
Default
21
o2Ac
Out 2 action
0
dir =
Direct action
rEU =
Reverse action
dir.r =
Direct with reversed LED
ReU.r = Reverse with reversed LED
dir
22
o3F
Out 3 function
0
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL =
Alarm output
t.out = Reserved
t.HoF = Reserved
P.End = Reserved
P.HLd = Reserved
P.uit = Reserved
P.run = Reserved
P.Et1 = Reserved
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on =
Out 3 always ON
riSP = Inspection requested (the worked hours/days
counter has reached the programmed threshold)
AL
23
o3AL
Alarms linked up with the out 3
0
0 to 63
+1 =
Alarm 1
+2 =
Alarm 2
+4 =
Alarm 3
+8 =
Loop break alarm
+16 =
Sensor Break
+32 =
Overload on output 4
AL2
24
o3Ac
Out 3 action
0
dir =
Direct action
rEU =
Reverse action
dir.r =
Direct with reversed LED
ReU.r = Reverse with reversed LED
dir
25
o4F
Out 4 function
0
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL =
Alarm output
t.out = Reserved
t.HoF = Reserved
P.End = Reserved
P.HLd = Reserved
P.uit = Reserved
P.run = Reserved
P.Et1 = Reserved
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
AL
26
o4AL
Alarms linked up with the out 4
0
0 to 63
+1 =
Alarm 1
+2 =
Alarm 2
+4 =
Alarm 3
+8 =
Loop break alarm
+16 =
Sensor Break
+32 =
Overload on output 4
AL1 +
AL2
27
o4Ac
Out 4 action
0
dir =
Direct action
rEU =
Reverse action
dir.r =
Direct with reversed LED
ReU.r = Reverse with reversed LED
dir