Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 7
4.
Using
and
buttons set the code 1 value
according to the following tables.
L M N O
Prepare your code 1
Input Type and Range
L
M
TC J
-50 to +1000°C
0
0
TC K
-50 to +1370°C
0
1
TC S
-50 to 1760°C
0
2
TC R
-50 to +1760°C
0
3
TC T
-70 to +400°C
0
4
PT 100
-200 to +850°C
0
7
PT 1000
-200 to +850°C
0
8
Linear 0 to 60 mV
0
9
Linear 12 to 60 mV
1
0
Linear 0 to 20 mA (this selection forces Out 4 = TX)
1
1
Linear 4 to 20 mA (this selection forces Out 4 = TX)
1
2
Linear 0 to 5 V
1
3
Linear 1 to 5 V
1
4
Linear 0 to 10 V
1
5
Linear 2 to 10 V
1
6
TC J
-58 to +1832°F
1
7
TC K
-58 to +2498°F
1
8
TC S
-58 to 3200°F
1
9
TC R
-58 to +3200°F
2
0
TC T
-94 to +752°F
2
1
PT 100
-328 to +1562°F
2
4
PT 1000
-328 to +1562°F
2
5
L M N O
c%d1
:
Control mode
OP1
OP2
OP3
OP4
N
O
ON/OFF heating = H
H
AL1
AL2
AL3
0
0
NU
AL1
AL2
H
0
1
ON/OFF cooling = C
C
AL1
AL2
AL3
0
2
NU
AL1
AL2
C
0
3
ON/OFF with neutral
zone (H/C)
H
C
AL2
AL3
0
4
H
AL1
AL2
C
0
5
C
H
AL2
AL3
0
6
NU
H
AL2
C
0
7
C
AL1
AL2
H
0
8
NU
C
AL2
H
0
9
PID heating = H
H
AL1
AL2
AL3
1
0
NU
AL1
AL2
H
1
1
PID cooling = C
C
AL1
AL2
AL3
1
2
NU
AL1
AL2
C
1
3
PID double action (H/C)
H
C
AL2
AL3
1
4
H
AL1
AL2
C
1
5
C
H
AL2
AL3
1
6
NU
H
AL2
C
1
7
C
AL1
AL2
H
1
8
NU
C
AL2
H
1
9
5.
Push the
button.
The upper display shows
cod2
flashing while the lower
display shows
0000
or the
cod2
value stored in memory.
6.
Using
and
buttons set the code 2 value
according to the following tables.
P Q R S
Prepare your code 2
Alarm 3
R
Alarm 2
Q
Alarm 1
P
Not used
0
0
0
Sensor break
1
1
1
Absolute
High
2
2
2
Low
3
3
3
Absolute High/Low
External High/Low
4
4
4
Internal High/Low
5
5
5
Deviation
Deviation high
6
6
6
Deviation low
7
7
7
Band
External band
8
8
8
Internal band
9
9
9
P Q R S
c%d2
:
Auxiliary functions activation
S
None
0
Wattmeter (instantaneous power expressed in W)
1
Wattmeter (energy expressed in Wh)
2
Absolute worked time (expressed in days)
3
Absolute worked time (expressed in hours)
4
7.
Push the
button.
If the just entered codes are accepted, the upper display
shows
code
while the lower display shows
good
.
8.
Push the
button to save the configuration code and
exit the Code configuration procedure.
Note:
After using the “
Code configuration
” method, it will
always be possible to modify the parameters using the
“
Complete configuration
” method. If the value of a
parameter among those included in the configuration
codes (
cod1
-
cod2
) gets modified, the instrument
will acquire the change while maintaining all the other
parameters.
WARNING!
After a parameter change made as described
in the previous “Note”, when retrieving the
configuration codes (
cod1
-
cod2
), the lower
display will show “
oFF
” to alert the operator that
one of the parameters has been changed.