Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 32
]
PAn group - Operator HMI parameters
no. Param.
Description
Dec.
Point
Values
Default
118 PAS2
Level 2 password (limited
access level)
0
- oFF (Level 2 not protected by password);
- 1 to 200.
20
119 PAS3
Level 3 password (com-
plete configuration level)
0
3 to 200
30
120 PAS4
Level 4 password (CODE
configuration level)
0
201 to 400
300
121 uSrb
button function during
RUN TIME
nonE = No function;
tunE = Auto-tune/self-tune enabling. A single press (longer than 1 se-
cond) starts the auto-tune;
oPLo = Manual mode. The first pressure puts the instrument in manual mode
(OPLO) while a second one puts the instrument in Auto mode;
AAc = Alarm reset;
ASi =
Alarm acknowledge;
chSP = Sequential set point selection;
St.by = Stand by mode. The first press puts the instrument in stand by
mode while a second one puts the instrument in Auto mode;
Str.t =
Reserved;
P.run = Reserved;
P.rES = Reserved;
P.r.H.r = Reserved.
tunE
122 diSP
Display management
nonE = Standard display;
Pou =
Power output;
SPF = Final set point;
SPo = Operative set point;
AL1 =
Alarm 1 threshold;
AL2 =
Alarm 2 threshold;
AL3 =
Alarm 3 threshold;
Pr.tu = Reserved;
Pr.td = Reserved;
P.t.tu = Reserved;
P.t.td = Reserved;
ti.uP = Reserved;
ti.du = Reserved;
PErc = Percent of the power output used during soft start (when the soft
start time is equal to infinite, the limit is ever active and it can be
used also when ON/OFF control is selected);
PoS = Reserved.
0
123 di.cL
Display colour
0 = The display colour is used to show the actual deviation (PV - SP);
1 = Display red (fix);
2 = Display green (fix);
3 = Display orange (fix).
0
124 AdE
Deviation for display col-
our management
1 to 999 (E.U.)
5
125 di.St
Display Timeout
2
- oFF (display always ON);
- 0.1 to 99.59 (mm.ss).
oFF
126 fiLd
Filter on the displayed
value
1
- oFF (filter disabled)
- From 0.0 (oFF) to 20.0 (E.U.)
oFF
128 dSPu
Instrument status at
power ON
AS.Pr = Starts in the same way it was prior to the power down;
Auto = Starts in Auto mode;
oP.0 = Starts in manual mode with a power output equal to zero;
St.bY = Starts in stand-by mode.
AS.Pr
129 oPr.E
Operative modes enabling
ALL =
All modes will be selectable by the next parameter;
Au.oP = Auto and manual (OPLO) mode only will be selectable by the next
parameter;
Au.Sb = Auto and Stand-by modes only will be selectable by the next parameter.
ALL
130 oPEr
Operative mode selection
If oPr.E = ALL:
- Auto = Auto mode;
-
oPLo = Manual mode;
-
St.bY = Stand by mode.
If oPr.E = Au.oP: -
Auto = Auto mode;
- oPLo = Manual mode.
If oPr.E = Au.Sb:
- Auto = Auto mode;
-
St.bY = Stand by mode.
Auto