Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 31
no. Param.
Description
Dec.
Point
Values
Default
59
SELF
Self tuning enabling
0
no =
The instrument does not perform the self-tuning
YES = The instrument is performing the self-tuning
no
60
HSEt
Hysteresis of the ON/OFF control
dP
0 to 9999 (E.U.)
1
61
cPdt
Time for compressor protection
0
From 0 (oFF) to 9999 (s)
oFF
62
Pb
Proportional band
dP
1 to 9999 (E.U.)
50
63
ti
Integral time
0
From 0 (oFF) to 9999 (s)
200
64
td
Derivative time
0
From 0 (oFF) to 9999 (s)
50
65
Fuoc
Fuzzy overshoot control
2
0.00 to 2.00
0.50
66
tcH
Heating output cycle time
1
0.1 to 130.0 (s)
20.0
67
rcG
Power ratio between heating and
cooling action
2
0.01 to 99.99
1.00
68
tcc
Cooling output cycle time
1
0.1 to 130.0 (s)
20.0
69
rS
Manual reset (Integral pre-load)
1
-100.0 to +100.0 (%)
0.0
70
Str.t
Servomotor stroke time
0
5 to 1000 seconds
60
71
db.S
Servomotor dead band
0
0 to 100%
50
72
od
Delay at power up
2
From 0.00 (oFF) to 99.59 (hh.mm)
oFF
73
St.P
Maximum power output used during
soft start
0
-100 to 100 (%)
0
74
SSt
Soft start time
2
- 0.00 (oFF);
- 0.01 to 7.59 (hh.mm);
- inF (always ON).
oFF
75
SS.tH
Threshold for soft start disabling
dP
-1999 to +9999 (E.U.)
9999
]
SP group - Set point parameters
no. Param.
Description
Dec.
Point
Values
Default
76
nSP
Number of used set points
0
1 to 4
1
77
SPLL
Minimum set point value
dP
From -1999 to SPHL
-1999
78
SPHL
Maximum set point value
dP
From SPLL to 9999
9999
79
SP
Set point 1
dP
From SPLL to SPLH
0
80
SP 2
Set point 2
dP
From SPLL to SPLH
0
81
SP 3
Set point 3
dP
From SPLL to SPLH
0
82
SP 4
Set point 4
dP
From SPLL to SPLH
0
83
A.SP
Selection of the active set point
0
From 1 (SP 1) to nSP
1
84
SP.rt
Remote set point type
0
RSP = The value coming from serial link is used as remote set point;
trin =
The value will be added to the local set point selected by
A.SP and the sum becomes the operative set point;
PErc = The value will be scaled on the input range and this value
will be used as remote SP.
trin
85
SPLr
Local/remote set point selection
0
Loc =
local;
rEn = remote.
Loc
86
SP.u
Rate of rise for
POSITIVE
set point
change (ramp UP)
2
0.01 to 99.99 (inF) Eng. units per minute
inF
87
SP.d
Rate of rise for
NEGATIVE
set point
change (ramp DOWN)
2
0.01 to 99.99 (inF) Eng. units per minute
inF