Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 29
]
AL1 group
no. Param.
Description
Dec.
Point
Values
Default
28
AL1t
Alarm 1 type
0
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
HiAb
29
Ab1
Alarm 1 function
0
0 to 15
+1 = Not active at power up
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 =
Relative alarm not active at set point change
0
30
AL1L
- For High and low alarms, it is the low limit
of the AL1 threshold;
- For band alarm, it is low alarm threshold
dp
From -1999 to AL1H (E.U.)
-1999
31
AL1H
- For High and low alarms, it is the high
limit of the AL1 threshold;
- For band alarm, it is high alarm threshold
dp
From AL1L to 9999 (E.U.)
9999
32
AL1
AL1 threshold
dp
From AL1L to AL1H (E.U.)
0
33
HAL1
AL1 hysteresis
dp
1 to 9999 (E.U.)
1
34
AL1d
AL1 delay
0
From 0 (oFF) to 9999 (s)
oFF
35
AL1o
Alarm 1 enabling during Stand-by mode and
out of range conditions
0
0 = Alarm 1 disabled during Stand by and out of range
1 = Alarm 1 enabled in stand by mode
2 = Alarm 1 enabled in out of range condition
3 = Alarm 1 enabled in stand by mode and in overrange
condition
0
]
AL2 group
no. Param.
Description
Dec.
Point
Values
Default
36
AL2t
Alarm 2 type
0
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
Loab
37
Ab2
Alarm 2 function
0
0 to 15
+1 = Not active at power up
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 =
Relative alarm not active at set point change
0
38
AL2L
- For High and low alarms, it is the low limit
of the AL2 threshold;
- For band alarm, it is low alarm threshold
dp
From -1999 to AL2H (E.U.)
-1999
39
AL2H
- For High and low alarms, it is the high
limit of the AL2 threshold;
- For band alarm, it is high alarm threshold
dp
From AL2L to 9999 (E.U.)
9999
40
AL2
AL2 threshold
dp
From AL2L to AL2H (E.U.)
0
41
HAL2
AL2 hysteresis
dp
1 to 9999 (E.U.)
1
42
AL2d
AL2 delay
0
From 0 (oFF) to 9999 (s)
oFF
43
AL2o
Alarm 2 enabling during Stand-by mode and
out of range conditions
0
0 = Alarm 2 disabled during Stand by and out of range
1 = Alarm 2 enabled in stand by mode
2 = Alarm 2 enabled in out of range condition
3 = Alarm 2 enabled in stand by mode and in overrange
condition
0