Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 26
Appendix A
]
inP GROUP - Main and auxiliary input configuration
no. Param.
Description
Dec.
Point
Values
Default
1
SEnS
Sensor selection
0
J = TC J,
crAL = TC K,
S = TC S,
r = TC R,
t = TC T,
Pt1 = RTD Pt100,
Pt10 = RTD Pt1000,
0.60 = 0 to 60 mV,
12.60 = 12 to 60 mV,
0.20 = 0 to 20 mA,
4.20 = 4 to 20 mA,
0.5 = 0 to 5 V,
1.5 = 1 to 5 V,
0.10 = 0 to 10 V,
2.10 = 2 to 10 V
J
2
dp
Decimal Point Position (linear inputs)
0
0 to 3
0
Decimal Point Position (different than linear inputs)
0/1
3
SSC
Initial scale read-out for linear inputs
dp
-1999 to 9999
0
4
FSc
Full Scale Readout for linear inputs
dp
-1999 to 9999
1000
5
unit
Engineer unit
°C/°F
°C
6
Fil
Digital filter on the measured value
1
0 (= OFF) to 20.0 s
1.0
7
inE
Sensor error used to enable the safety output
value
or = Over range
ou = Under range
our = Over and under range
our
8
oPE
Safety output value (% of the output)
-100 to 100
0
9
IO4.F
I/O 4 function
on =
Output used as PWS for TX,
out4 = Output 4 (digital output 4),
dG2c = Digital input 2 driven by contact,
dG2U = Digital input 2 driven by voltage
out4
10
diF1
Digital Input 1 function
oFF =
Not used,
1 =
Alarm reset,
2 = Alarm acknowledge (ACK),
3 = Hold of the measured value,
4 = Stand by mode,
5 = Manual mode,
6 = HEAt with SP1 and CooL with SP2,
7 to 17 = No action
18 = Sequential SP selection,
19 = SP1 - SP2 selection,
20 = SP1 to SP4 binary selection,
21 = Digital inputs in parallel to
and
keys
oFF
11
diF2
Digital Input 2 function
oFF
12
di.A
Digital Inputs Action
(DI2 only if configured)
0 = DI1 direct action, DI2 direct action
1 = DI1 reverse action, DI2 direct action
2 = DI1 direct action, DI2 reverse action
3 = DI1 reverse action, DI2 reverse action
0