Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 33
]
Ser group - Serial link parameters
no. Param.
Description
Dec.
Point
Values
Default
131 Add
Instrument address
- oFF
- 1 to 254
1
132 bAud
baud rate
1200 = 1200 baud
2400 = 2400 baud
9600 = 9600 baud
19.2 = 19200 baud
38.4 = 38400 baud
9600
133 trSP
Selection of the value to be
retransmitted (Master)
nonE = Retransmission not used (the instrument is a slave);
rSP =
The instrument becomes a Master and retransmits the operati-
ve set point;
PErc = The instrument become a Master and it retransmits the power
output.
nonE
]
COn group - Consumption parameters
no. Param.
Description
Dec.
Point
Values
Default
134 Co.tY
Count type
oFF = Not used;
1 = Instantaneous power (kW);
2 = Power consumption (kW/h);
3 = Reserved;
4 = Total worked days: number of hours the instrument is turned ON
divided by 24;
5 = Total worked hours: number of hours the instrument is turned ON;
6 = Total worked days with threshold: number of hours the instru-
ment is turned ON divided by 24, the controller is forced in stand-
by when Co.ty value reaches the threshold set in [137] h.Job;
7 = Total worked hours with threshold: number of hours the instru-
ment is turned ON, the controller is forced in stand-by when
Co.ty value reaches the threshold set in [137] h.Job;
8 = Totalizer of control relay worked days: number of hours the con-
trol relay has been in ON condition, divided by 24;
9 = Totalizer of control relay worked hours: number of hours the
control relay has been in ON condition;
10 = Totalizer of control relay worked days with threshold: number of
hours the control relay has been in ON condition divided by 24,
the controller is forced in stand-by when Co.ty value reaches the
threshold set in [137] h.Job;
11 = Totalizer of control relay worked hours with threshold: number of
hours the control relay has been in ON condition, the controller is
forced in stand-by when Co.ty value reaches the threshold set in
[137] h.Job.
oFF
135 UoLt
Nominal Voltage of the load
1 to 9999 (V)
230
136 cur
Nominal current of the load
1 to 999 (A)
10
137 h.Job
Threshold of the working
period
oFF =
threshold not used
0 to 9999 days (when [133] cotY = 4)
0 to 9999 hours (when [133] cotY = 5)
0
138 t.Job
Worked time (not resettable)
0 to 9999 days
]
CAl group - User calibration parameters
no. Param.
Description
Dec.
Point
Values
Default
139 AL.P
Adjust Low Point
From -1999 to (AH.P - 10) in engineering units
0
140 AL.o
Adjust Low Offset
-300 to +300 (E.U.)
0
141 AH.P
Adjust High Point
From (AL.P + 10) to 9999 engineering units
9999
142 AH.o
Adjust High Offset
-300 to +300
0