App.1-24
TI 32S01J30-01E
Appendix 1. US (FM) NI/Canada (FM) NI/IECEx Ex “ec”/ECAS-EX Ex “ec”
Yokogawa Electric Corporation
Model
ProSafe-RS N-IO
Title
Control drawing
No.
NIE009-A101
Page
2
Revision
15
(Continued)
Classifications
Model
Ambient Temperature (*1)
Safety Node Units
S2NN30D-4
□
0
□
00013
−40 to 70 °C
S2NN30D-4
□
0
□
00113
S2NN30D-4
□
0
□
01113
S2NN30D-4
□
0
□
02113
S2NN30D-4
□
0
□
00213
S2NN30D-4
□
0
□
01213
S2NN30D-4
□
0
□
02213
S2NN30D-4
□
0
□
01013
S2NN30D-4
□
0
□
02013
−40 to 70 °C (altitude ≤ 2000 m)
−40 to 60 °C (2000 m < altitude ≤ 3000 m)
S2BN1D-
□
0130
S2BN1D-
□
1130
S2BN1D-
□
2130
−40 to 70 °C
When utilizing Digital output function of
S2MMM843, the total load current of all
channels is limited as shown below according
to the derating specifications due to the
ambient temperature of modules.
−40 to 40 °C: Max. 10.56 A
40 to 50 °C: Max.9.71 A
50 to 60 °C: Max.8.85 A
60 to 70 °C: Max.8 A
S2BN1D-
□
9130
−40 to 70 °C (*5)
When utilizing Digital output function of
S2MMM843, the total load current of all
channels is limited as shown below according
to the derating specifications due to the
ambient temperature of modules.
−40 to 40 °C: Max. 10.56 A
40 to 50 °C: Max.9.71 A
50 to 60 °C: Max.8.85 A
60 to 70 °C: Max.8 A
Power supply module
S2PW503-S0130
−40 to 70 °C
S2PW504-S0130
Bus interface module
S2EN402-S0011
−20 to 70 °C
S2EN404-S0011
S2EN501-S00130
−40 to 70 °C
S2EN501-S01130
S2EN501-S11130
S2EN501-S21130
S2EN501-S02130
S2EN501-S12130
S2EN501-S22130
S2EN501-S10130
S2EN501-S20130
−40 to 70 °C (altitude ≤ 2000 m)
−40 to 60 °C (2000 m < altitude ≤ 3000 m)
Dec. 3, 2021-00