App.1-17
TI 32S01J30-01E
Appendix 1. US (FM) NI/Canada (FM) NI/IECEx Ex “ec”/ECAS-EX Ex “ec”
Yokogawa Electric Corporation
Model
ProSafe-RS/ProSafe-RS Lite
Title
Control drawing
No.
NFM014-A13
Page
16
Revision
78
Nonincendive Field Wiring Parameters (Input parameters) (*1)
Model
Vmax
(V)
Imax
(mA)
Ci
(μF)
Li
(μH)
Remarks
SAI143
L1AI143
Redundant
26.4
26
0.008
20
-4-wire transmitter input
-Included terminal block and terminal
board but excluded cable
Single
26.4
26
0.004
20
SAV144
L1AV144
Redundant
30
0.6
0.001
10
-Input
-Included terminal block and terminal
board but excluded cable
Single
30
0.3
0.001
10
SAT145
L1AT145
Redundant
5
1.53
0.6
10
-TC/mV input
-Included terminal board but excluded
cable
Single
5
1.53
0.6
10
SBD2D
60
20
0
0
Ready input DC
SBD3D
60
20
0
0
Ready input DC
SBD4D
60
20
0
0
Ready input DC
S1BB4D
60
20
0
0
Ready input DC
*1 These parameters are applied to all modes of each model if the mode is not otherwise
remarked.
Cable Parameter
Model
L
(μH/m)
C
(pF/m)
Remark
KS1
1.5
110
AKB331
1.5
110
AKB611
2.0
200
Dec. 3, 2021-00