App.3-3
TI 32S01J30-01E
Appendix 3. IECEx Ex “ec”/ IECEx Type “n” of S2BN4D / S2BN5D
Appendix 3.2 IECEx Ex “ec”/ Intrinsic Safety/
ECAS-Ex Ex “ec” Information of S2BN5D
Applicable Standards
IEC 60079-0 Ed. 7.0 (2017)
IEC 60079-7 Ed. 5.1 (2017)
IEC 60079-11 Ed.6.0 (2011)
Markings
IECEx EXA 15.0003X
Ex ec [ia Ga] IIC T4 Gc
Applicable Models
S2BN5D
List of Parameters
Table List of Parameters (IECEx) of Base Plate for Barrier (S2BN5D)
Modules
Uo (V)
Io (mA)
Po (mW)
Ui (V)
Co (nF)
Lo (mH)
Remarks
S2BN5D
30
—
—
30
—
—
(*1)
*1:
The used P+F’s I.S. barriers determine the ultimate output parameters of the channel. Please refer to P+F’s instruction manual
for the parameter of P+F’s I.S. barriers.
Installation specifications
• Ambient temperature -20 degree C to 70 degree C
• Ambient humidity 5 to 95%RH (no condensation)
• Location Indoor use
• Power supply
System power supply : 24 V DC +10 %/-14 %
Barrier power supply : 24 V DC +20 %/-10 %, up to 1.8 A