2. Explosion Protection Instrumentation in Zone 2/Division 2
2-8
TI 32S01J30-01E
Example
As an example, we show the case where SAI143 I/O module, a power input module and EJA,
a differential pressure transmitter of Yokogawa Electric Corporation are connected. EJA is
connected to circuit of SAI143 via 100 m cable, and installed in Class I, Division 2 hazardous
area.
Power
Supply
Lc
Cc
Li
Ci
Device that gives energy
(The source device)
Device that receives energy
(The load device)
F020103E.ai
Hazardous area (Class I, Division 2)
<SAI143>
<Differential pressure transmitter EJA>
The defined parameters have the following values.
(Voc) = 26.4 V
(Isc) = 26 mA
(Ca) = 0.13 μF
(La) = 10 mH
and,
(Cc) = 200 pF/m
100 m = 0.0002 μF
100 = 0.02 μF
(Lc) = 0.66 μH/m
100 m = 0.00066 mH
100 = 0.066 mH
therefore,
Voc = 26.4 V
<
Vmax = 30 V
Isc = 26 mA
<
Imax = 165 mA
Ca = 0.13 μF
>
Ci + Cc = 0.0425 μF
La = 10 mH
>
Li + Lc =0.796 mH
As the results above meet the combinational conditions, we can conclude that a field wiring can be installed
in accordance with a general wiring construction.
(Vmax) = 30 V
(Imax) = 165 mA
(Ci) = 0.0225 μF
(Li) = 0.73 mH
+
-
+
-
Figure Connection of SAI143 and EJA
Dec. 3, 2021-00