App.1-39
TI 32S01J30-01E
Appendix 1. US (FM) NI/Canada (FM) NI/IECEx Ex “ec”/ECAS-EX Ex “ec”
Yokogawa Electric Corporation
Model
ProSafe-RS N-IO
Title
Instructions (IECEx)
No.
NIE009-A102
Page
2
Revision
15
(Continued)
Classifications
Model
Ambient Temperature (*1)
Safety Node Units
S2BN1D-
□
0130
S2BN1D-
□
1130
S2BN1D-
□
2130
−40 to 70 °C
When utilizing Digital output function of
S2MMM843, the total load current of all
channels is limited as shown below according
to the derating specifications due to the
ambient temperature of modules.
−40 to 40 °C: Max. 10.56 A
40 to 50 °C: Max.9.71 A
50 to 60 °C: Max.8.85 A
60 to 70 °C: Max.8 A
S2BN1D-
□
9130
−40 to 70 °C (*5)
When utilizing Digital output function of
S2MMM843, the total load current of all
channels is limited as shown below according
to the derating specifications due to the
ambient temperature of modules.
−40 to 40 °C: Max. 10.56 A
40 to 50 °C: Max.9.71 A
50 to 60 °C: Max.8.85 A
60 to 70 °C: Max.8 A
Power supply module S2PW504-S0130
−40 to 70 °C
Bus interface module
S2EN402-S0011
−20 to 70 °C
S2EN404-S0011
S2EN501-S00130
−40 to 70 °C
S2EN501-S01130
S2EN501-S11130
S2EN501-S21130
S2EN501-S02130
S2EN501-S12130
S2EN501-S22130
S2EN501-S10130
S2EN501-S20130
−40 to 70 °C (altitude ≤ 2000 m)
−40 to 60 °C (2000 m < altitude ≤ 3000 m)
I/O module
S2MMM843-SS1130
S2MDV843-0S1130
−40 to 70 °C (*4)
When utilizing Digital output function, the total
load current of all channels is limited as
shown below according to the derating
specifications due to the ambient temperature
of modules.
−40 to 40 °C: Max. 10.56 A
40 to 50 °C: Max.9.71 A
50 to 60 °C: Max.8.85 A
60 to 70 °C: Max.8 A
S2DCV02-0
−40 to 70 °C (*4)
Terminal board
A2BM4-130
−40 to 70 °C (*5)
Power Cable
S2KPB10-C
□□□
−40 to 70 °C (*4)
Bus cable
S2KLF10-1
□□
2
□
−40 to 70 °C (*4)
Dec. 3, 2021-00