5-14
<Toc>
<5. Parameters>
IM 05D01C12-41E
4th Edition: May 31, 2006-00
●
Input-/Output-related Parameters
-19999 to 30000,
however SL < SH, SH-SL
30000
Set the read-out scale of voltage-mode PV input.
OFF (0)
PV input unit
% (0): Percent
°
F (5): Fahrenheit
°
C (1): degree Celsius
- (2): No unit
°
C (1)
Max. value of PV input
range
Min. value of PV input
range
Max. value of
instrument
input range
Min. value of
instrument
input range
Set the PV input range, however RL < RH
-Temperature input
Set the range of temperature that is actually controlled.
- Voltage input
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually
controlled should be set using the parameters
Maximum Value of PV Input Scale (SH) and Minimum
Value of PV Input Scale (SL).
PV input decimal point
position (displayed
at voltage input)
Max. value of PV input
scale
(displayed at voltage input)
Min. value of PV input
scale
(displayed at voltage input)
Selection of PV input
burnout action
Presence/absence of
PV input reference
junction compensation
0 to 4
Set the position of the decimal point of voltage-
mode PV input.
2
100.00
0.00
OFF (0)
UP (1): Up scale
DOWN (2): Down scale
-
OFF (0), ON (1)
-
41
(IN)
(UNI)
(RH)
(RL)
(DP)
(SH)
(SL)
(BSL)
(RJC)
(RSP)
PV input type (PV INPUT
terminals)
- - terminals
13
12
11
Remote input type
(RSP INPUT terminals)
- terminals
21 22
OFF (0), 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56
See Instrument Input Range Codes in
“2. Initial Settings.”
40, 41, 50, 51
See Instrument Input Range Codes in
“2. Initial Settings.”
Max. value of remote
setting input scale
Min. value of remote
setting input scale
Selection of non-display
of figures below PV input
decimal point
Max. value of
PV input range
or that of PV
input scale
Min. value of
PV input range
or that of PV
input scale
-19999 to 30000
However, RSL < RSH
, RSH-RSL
30000
Set RSL and RSH in a range of RL to RH or
SL to SH.
OFF (0), ON (1)
For second decimal place, figures up to the
first decimal place are shown.
OFF (0)
(RSH)
(RSL)
(DPC)
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value