3-6
<Toc>
<3. Operations>
IM 05D01C12-41E
4th Edition: May 31, 2006-00
[TIP]
The PID parameter numbers set in step 4.
should be set as follows:
In case of PID for 1.SP, PID = 1Gr
In case of PID for 2.SP, PID = 2Gr
In case of PID for 3.SP, PID = 3Gr
In case of PID for 4.SP, PID = 4Gr
Note:
For use of 5.SP or more, set the PID param-
eter numbers in the same way as those
above.
9.
Press the
S E T / E N T
key for more than 3 sec-
onds. This returns you to the display
shown at power-on (figure below).
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays PV.
Displays
target setpoint-1
“1.SP”.
3.5
Setting Alarm Setpoints
The following operating procedure describes an example of setting 160.0 to alarm-1
setpoint. Check alarm type before setting the alarm setpoint. To change alarm type, see
“2.7 Changing Alarm Type.”
Alarm output terminals
Factory-shipped settings
Alarm-1 (terminal numbers )............PV high limit alarm
Alarm-2 (terminal numbers )............PV low limit alarm
Alarm-3 (terminal numbers )............PV high limit alarm
Alarm-4 (terminal numbers )............PV low limit alarm
-
6
7
-
5
7
-
4
7
-
34
35
1.
Bring the operating display into view
(display appears at power on).
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays PV.
Displays
target setpoint-1
“1.SP”.
2.
Press the
S E T / E N T
key for more than 3
seconds to call up the menu “OP.PA”.
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
menu “OP.PA”.
Displays
symbol “D-U”.
3.
Press the
S E T / E N T
key once to display
parameter “A1”.
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
parameter
“A1”.
4.
Press the
or
key to display the
required setpoint.
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Blinks during
change.