<Toc>
<1. Installation>
1-11
IM 05D01C12-41E
4th Edition: May 31, 2006-00
Construction, Installation, and Wiring
•
Construction: Dust-proof and drip-proof pront panel conforming to IP55. For side-by-
side close installation the controller loses its dust-proof and drip-proof protection.
•
Material: ABS resin and polycarbonate
•
Case color: Black
•
Weight: About 1 kg or less
•
Dimensions:
UT450
96 (W)
96 (H)
100 (depth from panel face) mm
UT420
48 (W)
96 (H)
100 (depth from panel face) mm
•
Installation: Panel-mounting type. With top and bottom mounting hardware (1 each)
•
Panel cutout dimensions:
UT450
92
0
+0.8
(W)
92
0
+0.8
(H) mm
UT420
45
0
+0.6
(W)
92
0
+0.8
(H) mm
•
Installation position: Up to 30
upward facing (not designed for facing downward)
•
Wiring: M3.5 screw terminals (for signal wiring and power/ground wiring as well)
Power Supply Specifications
•
Power supply: Rated voltage of 100 to 240 V AC (
10%), 50/60 Hz
•
Power consumption: Max. 20 VA (8.0 W max.)
•
Internal fuse rating: 250 V AC, 1.6A time-lug fuse
•
Data backup: Non-volatile memory (can be written to up to 100,000 times)
•
Withstanding voltage
-
Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute
-
Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute
-
Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
-
Between secondary terminals**:
At least 500 V AC for 1 minute
*
Primary terminals indicate power terminals and relay output terminals
** Secondary terminals indicate analog I/O signal, voltage pulse output, and contact
input terminals
•
Insulation resistance: 20 M
or more at 500 V DC between power terminals and
grounding terminal
•
Grounding: Class D grounding (grounding resistance of 100
or less)