<2. Initial Settings>
2-9
IM 05D01C12-41E
4th Edition: May 31, 2006-00
2.4
Setting Control Output Type
(except for a Position
Proportional Controller)
The following operating procedure describes an example of changing time proportional PID
relay output (0: factory-shipped value) to current output (2).
Control output terminal
Values in parentheses are setpoints
Time proportional PID relay (0)/on-off(3) output...........................
Current (2)/time proportional PID voltage pulse (1) output............
-
-
1
2
3
-
16 17
For details on the output terminals for heating/cooling control, see
“1.5 Terminal Wiring Diagrams.”
1.
Bring the operating display into view
(display appears at power on).
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
target setpoint-1
“1.SP”.
Displays PV.
2.
Press the
S E T / E N T
key for more than 3 sec-
onds to call up the menu “OP.PA”.
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
symbol “D-U”.
Displays
menu “OP.PA”.
3.
Press the
key once to display the
menu “STUP”.
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
menu “STUP”.
4.
Press the
S E T / E N T
key once to display the
menu “SP”.
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
menu “SP”.
5.
Press the
key six times to display the
menu “I/O”.
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
menu “I/O”.
6.
Press the
S E T / E N T
key several times to
display the parameter “OT” (control output
type).
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
parameter
“OT”.