<T
oc>
<1. Installation>
1-15
IM 05D01C12-41E
4th Edition: May 31, 2006-00
■
UT450 Standard Type (Model UT450-0
䊐
or UT450-3
䊐
) or Heating/Cooling Type (Model UT450-2
䊐
)
1
2
3
4
5
6
7
8
9
10
41
42
43
44
45
46
47
48
49
50
31
32
33
34
35
36
21
22
23
24
25
26
27
11
12
13
14
15
16
17
16
17
Current/voltage
pulse output
4-20 mA DC,
voltage pulse
(12 V)
Control output
8
9
Power supply
10
L
N
Allowable range: 100 to 240 V AC (
10%)
(free voltage)
50/60 Hz shared
Power supply
12
13
TC input
11
12
RTD input
13
12
13
mV/V input
21
22
Remote input
* Wiring can only be carried out for
controllers with remote input.
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
23
24
RS-485 communication * Wiring can only be carried out
for controllers with communication
functions.
Maximum baud rate: 9600 bps
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
19
18
Correspondence between DIS parameters and external contact input functions
40
39
38
37
20
28
30
When DIS=4
DI1
DI2
DI3
DI4
DI5
DI6
COM
COM
R/L
STOP when DI3=ON
RUN when DI3=OFF
AUTO when DI4=ON
MAN when DI4=OFF
No function
No function
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=3
STOP when DI1=ON
RUN when DI1=OFF
2.SP when DI2=ON
1.SP when DI2=OFF
AUTO when DI3=ON
MAN when DI3=OFF
No function
No function
No function
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=2
AUTO when DI1=ON
MAN when DI1=OFF
2.SP when DI2=ON
1.SP when DI2=OFF
STOP when DI3=ON
RUN when DI3=OFF
No function
No function
No function
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=1 (Factory-set default)
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
DI3
DI4
1.SP2.SP 3.SP4.SP
ON
ON
OFF
OFF
ON
ON OFF
OFF
5.SP 6.SP7.SP 8.SP
ON
ON
OFF
OFF
ON
ON OFF
OFF
DI5
DI6
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Common
Remote when R/L=ON
Local when R/L=OFF
Common
When DIS=0
No function
No function
No function
No function
No function
No function
No function
Remote when R/L=ON
Local when R/L=OFF
Common
When switching target
SP 1 to 4:
DI1
DI2
1.SP 2.SP3.SP 4.SP
OFF
OFF
OFF
ON
ON
ON
OFF
ON
When switching target SP 1 to 8:
* If all of the contact inputs are set to OFF,
the controller uses the immediately
preceding target setpoint.
19
18
40
39
38
37
20
28
30
DI1
DI2
DI3
DI4
DI5
DI6
COM
COM
R/L
+5V
+5V
+5V
+5V
+5V
+5V
+5V
Contact
Transistor contact
* DIS is a setup parameter.
Changing DIS setpoint allows you to change the function of external contact input.
Contact rating: 12 V DC, 10 mA or more
6
5
Alarm output
4
7
34
35
AL1
AL2
AL3
COM
AL4
COM
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Transistor contact rating: 24 V DC, 50 mA
14
15
Retransmission output
4-20 mA DC
14
15
15 V DC loop power supply
14.5-18.0VDC
(21 mA DC max.)
* PV retransmission is configured at factory
before shipment.
Load resistance: 600
Ω
or less
* If 15 V DC loop power supply is used,
retransmission output cannot be used.
24 V DC loop
power supply
* Wiring can only be carried out for controllers with
24 V DC loop power supply.
1
2
Relay contact output
3
Control output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Note: Select this option from
the OT parameter.
*Time proportional PID relay contact
output is configured at factory
before shipment.
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
Relay
Transistor
A
b
B
Common
Alarm-1 output
Alarm-2 output
Alarm-3 output
Common
Alarm-4 output
-
+
+
-
-
+
-
+
-
+
-
+
21.6-28.0VDC
(30 mA DC max.)
43
44
+
-
OT=0 (factory-set default)
Time proportional control
Relay output (terminals , and )
OT=1
Correspondence between parameter OT and control output types
Time proportional control
Voltage pulse output (terminals and )
OT=2
Current output
(terminals and )
OT=3
On-off control
Relay output (terminals , and )
* OT is a setup parameter.
You can change the settings of the parameter OT to change the
control output type.
See “2. Initial Settings,” for more information.
Default: 1-5 V DC
UT
UT
1
2
3
16
17
16
17
1
2
3
12
13
Note: Connecting a 250
Ω
resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
䊏
Receiving 4-20 mA DC Current
Signals with the Controller
250
Ω
4-20mA
PV input * Not configured at factory before shipment
See “2. Initial Settings,” for more
information.
-
+
* Alarm-4 output is
optional function
37
38
39
40
28
29
30
18
19
20
Note:Select this option
from the OT
parameter.
Note: External Contact Input
If the power is turned on when the external contact input is OFF,
the mode (SPN, R/L, or A/M) existing before the power is turned
off will be continued. (except for RUN/STOP)