<1. Installation>
IM 05D01C12-41E
4th Edition: May 31, 2006-00
Signal Isolations
•
PV input terminals: Isolated from other input/output terminals. Not isolated from the
internal circuit.
•
Remote input terminals: Isolated from other input/output terminals and the internal
circuit.
•
15 V DC loop power supply terminals: Not isolated from 4-20 mA analog output nor
voltage pulse control output. Isolated from other input/output terminals and internal
circuit.
•
24 V DC loop power supply terminals: Isolated from 15 V DC loop power supply
terminals, 4-20 mA analog output terminals, voltage pulse control output terminals,
other input/output terminals and the internal circuit.
•
4-20 mA analog output terminals (for control output and retransmission): Not isolated
between 4-20 mA outputs nor from 15 V DC loop power supply and voltage pulse
control output. Isolated from other input/output terminals and internal circuit.
•
Voltage pulse control output terminals: Not isolated from 4-20 mA outputs nor 15 V DC
loop power supply. Isolated from other input/output terminals and internal circuit.
•
Relay contact control output terminals: Isolated between contact output terminals and
from other input/output terminals and internal circuit.
•
Contact input terminals: Not isolated between contact input terminals and from com-
munication terminals. Isolated from other input/output terminals and internal circuit.
•
Relay contact alarm output terminals: Not isolated between relay contact alarm
outputs. Isolated from other input/output terminals and internal circuit.
•
Transistor contact alarm output terminals: Not isolated between transistor contact
alarm outputs. Isolated from other input/output terminals and internal circuit.
•
RS-485 communication terminals: Not isolated from contact input terminals. Isolated
from other input/output terminals and internal circuit.
•
Feedback slide resistance input terminals: Not isolated from 4-20 mA analog output
terminals (control, retransmission), 15 V DC loop power supply, and voltage pulse
control outputs. Isolated from other input/output terminals and internal circuit.
•
Power terminals: Isolated from other input/output terminals and internal circuit.
•
Grounding terminals: Isolated from other input/output terminals and internal circuit.