9-19
IM 04P01B01-01E
Operations Related to the Computation Function (/M1 Option)
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
9.11 Setting the Alarm Delay Duration
This section explains the details of setting the duration of the delay high limit and delay
low limit alarms.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Press the
key or
SHIFT
+
key to select
Math
and then press the key.
3.
Press the
key or
SHIFT
+
key to select
Aux
and then press the key.
4.
Press the
key or
SHIFT
+
key to select
Alm delay
T
and then press the
key.
5.
Set each item and press the key.
Use the
key or
SHIFT
+
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC
key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
6.
When the
Setting complete
screen appears, do either of the following:
Press the key to set other channels.
If you are done, press the
ESC
key.
7.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Set the channel range.
The new setting takes effect.
ESC/?
Set the alarm delay time.
First channel Last channel
Set=Math
Math=Aux
Aux=Alm delay T
Duration= 10
CH=0A-0A
0A-0A Channel
Setting complete
Explanation
Duration
The duration can be set to a value in the range of 1 to 3600 s.
However, if the scan interval on the dot model is 2.5 s, the actual duration is an integer
multiple of 2.5 s. If the set value is not equal to an integer multiple of 2.5 s, the duration is
the smallest integer multiple of 2.5 s greater than the set value.
Example: The actual duration for 1 s and 2 s is 2.5 s.
<Related Topics>
Enabling the alarm delay function: Section 7.15