IM 04P01B01-01E
9-20
9.12 Setting the Timer Used in TLOG Computation
and Periodic Printout
This section explains the details of setting the timer used in TLOG computation and
periodic printout.
Basic Setting mode cannot be entered when recording is in progress or when
computation is in progress on models with the computation function (/M1 option).
Procedure
Changing the Settings
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the
and
keys simultaneously for 3 seconds to enter Basic
Setting mode.
3.
Press the
key or
SHIFT
+
key to select
Math
and then press the key.
4.
Press the key with
Timer (TLOG)
shown on the screen.
5.
Set each item and press the key.
Use the
key or
SHIFT
+
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC
key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
6.
When the
Setting complete
screen appears, do either of the following:
To correct the setting, press the key.
If you are done, press the
ESC
key.
Select the timer No.
The new setting takes effect.
ESC/?
Select the timer type.
(When the mode is set to Absolute)
Select the timer interval.
Set the reference time.
Select On to reset the computed
values every interval.
Select On to print the computed
values every interval.
Math Timer
Setting complete
Basic=Math
Math=Timer(TLOG)
Timer No.=1
Mode=Absolute
Interval=1h
Ref.Time=00:00
Reset=Off
Print=Off