1-3
IM 34M06H43-02E 2nd Edition : Sep.30, 2019-00
1.4 System Configuration
This section shows the configurable system configurations
1.4.1 Single-layer System
A single-layer system is a system with up to 32 modules connected twisted-pair
cables.
Be sure to install the FA Link module in a main unit. There is no restriction on the
installed position in the main unit.
The station numbers can be set to any number within the range of 01 to 32 provided
that no station numbers are duplicated (see Section 3.3, “Setting Station Numbers”).
Be sure to set station number 1 to a master station for network management
requirements. The stations numbers need not be sequential.
FA Link H2
FA Link H2
FA Link H2
FA Link H2/ FA Link H
FA Link H/ FA Link H2
A single-layer system in which F3LP32-0N and F3LP02-0N
modules coexist is not allowed.
Station1
F3LP32-0N
Station3
F3LP32-0N
Station32
F3LP32-0N
Station2
F3LP32-0N
Station1
F3LP32-0N
Station2
F3LP02-0N
Station3
F3LP32-0N
Station32
F3LP32-0N
FA Link H2
:
Represents the FA Link H2 Module (F3LP32-0N) or the FA Link H Module (F3LP02-0N)
Single-layer system consisting of F3LP32-0N modules
Figure 1.4.1 Single-layer System Configuration
CAUTION
F3LP32-0N modules cannot be connected to F3LP01-0N or F3LP02-0N modules.
This means that those modules cannot be used together in the same
communication bus (i.e., in the same system).