4-7
IM 34M06H43-02E 2nd Edition : Sep.30, 2019-00
■
For High-Speed Mode
The FA Link H2 supports high-speed mode for the FA Link module operation. As
compared to normal mode, high-speed mode:
- Reduces the response time
- Allows up to 1024 points of link devices per link system (maximum number of
modules that can be installed is 8).
(1)
Maximum response time of a single layer system (T
LD
)
T
LD
= ST
S
+ LR
S
2 + CT
3 + (ST
R
2) + (LR
R
2) + IM (unit: ms)
where,
ST
S
= Sequence program scan time of transmitting station
LR
S
= Link refresh time of transmitting station
CT = Cyclic transmission time
ST
R
= Sequence program scan time of transmitting station
LR
R
= Link refresh time of receiving station
IM = Internal processing time (constant: 30 ms)
Note:
The internal processing time of normal mode is 50 ms.
(2)
Link Refresh Time (LR)
LR = (RL
L
/16+RG
L
)
0.012
1.2 (unit: ms)
where,
RL
L
= Number of link relays used in the station
RG
L
= Number of link registers used in the station
(3)
Cyclic Transmission Time (CT)
CT = (RL
A
+ RG
A
16 + 200
S)
BT + 1.3
S + 8 (unit: ms)
where
RL
A
= Total number of link relays used in all stations
RG
A
= Total number of link registers used in all stations
BT = Transmission time per bit
BT = 0.0008 (1.25Mbps)
BT = 0.0016 (625kbps)
BT = 0.004 (250kbps)
BT = 0.008 (125kbps)
S = Total number of connected stations