3.6 Wiring
This section describes wiring for the FA Link H2 module.
■
Connector Pin Assignment
Pin
Terminal Name
5
SG
4
A
3
SHIELD
2
B
1
Unused
Figure 3.6.1 Connector Pin Assignment
CAUTION
- Connector pin assignment differs from that of the DeviceNet or YHLS module.
- Connector pin assignment differs from that of the F3LP02-0N.
- Connection of the communication cables must be carried out only when the
power of FA-M3 is OFF.
■
Attaching the Connector to the Module
Install heat-shrinkable tubing or adhesive vinyl tape after you attach ferrule terminals
or other terminals to the cables, and then connect the cables to the connector.
Insert ferrule terminals into each pin while pushing the protruding orange piece.
After this, make sure that the ferrule terminals will not come off from the connector.
In addition, check for short circuits, disconnections, and wrong connections by using
a tester or other means.
Insert the connector into the module as shown in Figure 3.6.2
Tighten the fixing screws with the appropriate tightening torque of 0.3 N·m.
Fastening
screw
Fastening
screw
Figure 3.6.2 Attaching the Connector to the Module
Pin 5
Pin 1